36
--- Ending of defrosting condition (meet one of the following is ok):
(1)Time of defrosting lasts 10 minutes.
(2) Temperature of outdoor coil T3 is up to 20°C.
8.3.2.6 High evaporator coil temp.T2 protection:
Model
TE7
TE8
TE9
MFE-60AMN1-RB4W
60
56
54
MFE-60ARN1-RB4W
(2T0043800026)
60
56
54
MFE-60ARN1-RB4W
(2T0043800036)
62
56
50
8.3.3 Cooling mode
8.3.3.1 Conditions for the compressor and outdoor fan action
MFE-60ARN1-RB4W(2T0043800036)
When compressor is on, outdoor fan will follow the below rules:
Fan(below): When compressor is on, the outdoor fan runs all the time.
Fan(above):
33
T3
On
Off
30
Condition
Compressor and outdoor fan
T1-Ts>1°C
On
T1-Ts
≤
0°C
Off