27
5.5 Wiring
Please refer to the Wiring Diagram.
Note: The power supply of the air conditioner is different according to the models.
Please refer to the WIRING DIAGRAM pasted on the indoor and outdoor units befo
re wire connection.
5.6 Test run
1.
Make sure the resistance between the socket of the electric system and the
grounded line, when detected by a 500 V million-ohmmeter, is at least 2 million ohms. If
the resistance is less than the number, please do not use the air conditioner;
2. Check again if the air conditioner is properly installed, especially for the anti-fallin
g device;
3. When accomplished all the above procedures, service people should explain and
test the air conditioner for the customer according to the "User's Manual".