UBC10.241, UBC10.241-N1
U
–
Series
24V, 10A, DC-UPS
May. 2008 / Rev. 1.1 DS-UBC10.241-EN
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time
unless otherwise noted. It is assumed that the input power source can deliver a sufficient output current.
www.pulspower.com Phone +49 89 9278 0 Germany
19/23
26.
R
EPLACEMENT OF THE BATTERY
The integrated battery should be replaced on a periodic basis, see chapter 28.1 for additional information.
The replacement should be done by qualified personnel trained on battery handling.
Caution! The terminals on the battery are always alive, therefore do not place items or tools on the battery!
How to replace the battery:
Step 1:
Remove
the fuse
before
working on
the unit.
Step 2:
Loosen the
captive cover
screw.
Step 3:
Remove the
battery-cover.
Step 4:
Disconnect the cables
from the battery
terminals.
Step 5:
Remove the
battery by pulling
on the strap.
Step 6:
Install the new battery.
Step 7:
Connect the red cable (+) to the red positive (+) terminal of the battery.
Step 8:
Connect the black cable (-) to the black negative (-) terminal of the battery.
Step 9:
Close the cover.
Step 10:
Tighten the screw.
Step 11:
Plug-in the fuse.
Disposal of batteries
Batteries marked with the recycling symbol should be recycled through a competent agency.
Replacement battery
See chapter 27 for information on the UZB12.051 or you can use a battery which meets the following requirements:
Battery type
nom.
12V, 4 to 6Ah
VRLA lead-acid maintenance free battery
Design life
min.
3 to 5 years
According to EUROBAT guideline
Dimensions
nom.
70x106x90mm
WxHxD *)
Pole connection
6.35mm/ 0.25Inch
Blade type; Fast-on
Approvals
UL, VdS
For applications which require UL or VdS
Allowed discharge current
min.
29A
Continuous
*)
Max. case height of 102mm
Содержание 4350006.71
Страница 1: ...thicknessCONTROL MTS 8201 LLT O Frame Non contact thickness measurement Operating Instructions ...
Страница 12: ...Page 12 Laser Safety thicknessCONTROL MTS 8201 LLT 4350006 71 ...
Страница 62: ...Page 62 Instruction Manual Software thicknessCONTROL MTS 8201 LLT 4350006 71 ...
Страница 64: ...Page 64 Pneumatic Plan thicknessCONTROL MTS 8201 LLT 4350006 71 ...
Страница 70: ...Page 70 Declaration of Incorporation thicknessCONTROL MTS 8201 LLT 4350006 71 ...
Страница 95: ...Operating Instructions scanCONTROL 29xx ...
Страница 99: ...scanCONTROL 29xx Appendix A 1 Accessories 60 A 1 1 Recommended Accessories 60 A 1 2 Optional Accessories 61 ...
Страница 100: ......
Страница 135: ...Page 41 Operation of the Sensor with a PC scanCONTROL 29xx Fig 24 Predefined measuring fields ...
Страница 193: ......
Страница 194: ......
Страница 229: ......