UBC10.241, UBC10.241-N1
U
–
Series
24V, 10A, DC-UPS
May. 2008 / Rev. 1.1 DS-UBC10.241-EN
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time
unless otherwise noted. It is assumed that the input power source can deliver a sufficient output current.
www.pulspower.com Phone +49 89 9278 0 Germany
3/23
5.
I
NPUT
Input
voltage
nom. DC
24V
Input
voltage
ranges
nom.
22.5 to 30Vdc
Continuous operation, see Fig. 5-1
30 to 35Vdc
Temporarily allowed, no damage to the DC-UPS *)
35Vdc
Absolute maximum input voltage with no damage to the
DC-UPS
0 to 22.5Vdc
The DC-UPS switches into buffer mode and delivers
output voltage from the battery if the input was above
the turn-on level before and all other buffer conditions
are fulfilled.
Allowed input voltage ripple
max. 1.5Vpp
Bandwidth
<400Hz
1Vpp
Bandwidth 400Hz to 1kHz
Allowed voltage between input
and earth (ground)
max. 60Vdc
or
42.4Vac
Turn-on voltage
typ.
22.8Vdc
The output does not switch on if the input voltage does
not exceed this level.
max. 23Vdc
Input
current
**)
typ.
120mA
Internal current consumption
typ.
1.1A
Current consumption for battery charging in constant
current mode at 24V input See Fig. 8-2 ***)
External capacitors on the input
No
limitation
*) The DC-UPS shows “Check Wiring” with the red LED and buffering is not possible
**) The total input current is the sum of the output current, the current which is required to charge the battery during the
charging process and the current which is needed to supply the DC-UPS itself. See also Fig. 5-2. This calculation does not apply
in overload situations where the DC-UPS limits the output current, therefore see Fig. 5-3.
***) Please note: This is the input current and not the current which flows into the battery during charging. The battery current can
be found in chapter 8.
Fig. 5-1
Input voltage range
Fig. 5-2
Input current, definitions
A: Rated input voltage range
B: Temp. allowed, no harm to the unit
C: Absolute max. input voltage
D: Buffer mode
V
IN
18
30
35V
22.5
0
A
B
C
D
V
OUT
Internal
current
consumption
Current
consumption
for battery
charging
Output
Current
Input
Current
Fig. 5-3
Input current and output voltage vs.
output current, typ. (battery fully charged)
Electronic output current limitation
The DC-UPS is equipped with an electronic output
current limitation. This current limitation works
in a switching mode which reduces the power
losses and heat generation to a minimum. As a
result, the output voltage drops since there is not
enough current to support the load. A positive
effect of the current limitation in switching mode
is that the input current goes down despite an
increase in the output current resulting in less
stress for the supplying source.
0
0
5
10
15
20A
Output Current
4
8
12
20A
Output Voltage
15
20V
Overload
Inp
ut
Cu
rre
nt
10
Содержание 4350006.71
Страница 1: ...thicknessCONTROL MTS 8201 LLT O Frame Non contact thickness measurement Operating Instructions ...
Страница 12: ...Page 12 Laser Safety thicknessCONTROL MTS 8201 LLT 4350006 71 ...
Страница 62: ...Page 62 Instruction Manual Software thicknessCONTROL MTS 8201 LLT 4350006 71 ...
Страница 64: ...Page 64 Pneumatic Plan thicknessCONTROL MTS 8201 LLT 4350006 71 ...
Страница 70: ...Page 70 Declaration of Incorporation thicknessCONTROL MTS 8201 LLT 4350006 71 ...
Страница 95: ...Operating Instructions scanCONTROL 29xx ...
Страница 99: ...scanCONTROL 29xx Appendix A 1 Accessories 60 A 1 1 Recommended Accessories 60 A 1 2 Optional Accessories 61 ...
Страница 100: ......
Страница 135: ...Page 41 Operation of the Sensor with a PC scanCONTROL 29xx Fig 24 Predefined measuring fields ...
Страница 193: ......
Страница 194: ......
Страница 229: ......