24V, 10A, DC-UPS
May. 2008 / Rev. 1.1 DS-UBC10.241-EN
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time
unless otherwise noted. It is assumed that the input power source can deliver a sufficient output current.
www.pulspower.com Phone +49 89 9278 0 Germany
9/23
12.
C
HECK
W
IRING AND
B
ATTERY
Q
UALITY
T
ESTS
The DC-UPS is equipped with an automatic “Check Wiring” and “Battery Quality” test.
“Check Wiring” test:
Under normal circumstances, an incorrect or bad connection from the battery to the DC-UPS or a missing (or blown)
battery fuse would not be recognized by the UPS when operating in normal mode. Only when back up is required
would the unit not be able to buffer. Therefore, a “check wiring” test is included in the DC-UPS. This connection is
tested every 10 seconds by loading the battery and analyzing the response from the battery. If the resistance is too
high, or the battery voltage is not in range, the unit displays “Check Wiring” with the red LED. At the same time the
green “Ready” LED will turn off.
“State of Health” (SoH) test:
The battery has a limited service life and needs to be replaced in a fixed interval which is defined by the specified
service life (acc. to the Eurobat guideline), based on the surrounding temperature and the number of
charging/discharging cycles. If the battery is used longer than the specified service life, the battery capacity will
degrade. Details can be found in chapter 28.1. SoH test can not determine a gradual loss in capacity. However, it can
detect a battery failure within the specified service life of the battery. Therefore a SoH-test is included in the DC-UPS.
The SoH test consists of different types of tests:
During charging:
If the battery does not reach the ready status (see chapter 14) within 30h, it is considered to be defective.
The reason could be a broken cell inside the battery.
During operation:
Once the battery is fully charged, a voltage drop test and a load test is performed alternately every 8 hours.
Three of the tests must consecutively produce negative results to indicate a battery problem.
A battery problem is indicated with the yellow LED (replace battery pattern) and the relay contact “Replace Battery”.
Please note that it can take up to 50 hours until a battery problem is reported. This should avoid nuisance error
messages as any urgent battery problems will be reported by the “Check Wiring” test and create a warning signal.
The battery tests require up to 50h uninterrupted operation. Any interruptions in the normal operation of the DC-
UPS may result in the “Replace Battery” test cycle to start over.
When “Replace battery” is indicated, it is recommended to replace battery as soon as possible.
Содержание 4350006.71
Страница 1: ...thicknessCONTROL MTS 8201 LLT O Frame Non contact thickness measurement Operating Instructions ...
Страница 12: ...Page 12 Laser Safety thicknessCONTROL MTS 8201 LLT 4350006 71 ...
Страница 62: ...Page 62 Instruction Manual Software thicknessCONTROL MTS 8201 LLT 4350006 71 ...
Страница 64: ...Page 64 Pneumatic Plan thicknessCONTROL MTS 8201 LLT 4350006 71 ...
Страница 70: ...Page 70 Declaration of Incorporation thicknessCONTROL MTS 8201 LLT 4350006 71 ...
Страница 95: ...Operating Instructions scanCONTROL 29xx ...
Страница 99: ...scanCONTROL 29xx Appendix A 1 Accessories 60 A 1 1 Recommended Accessories 60 A 1 2 Optional Accessories 61 ...
Страница 100: ......
Страница 135: ...Page 41 Operation of the Sensor with a PC scanCONTROL 29xx Fig 24 Predefined measuring fields ...
Страница 193: ......
Страница 194: ......
Страница 229: ......