background image

10

–––  STEP 6  –––

6.1 -  INSTALLING AND CONNECTING PH100 PHOTO-

CELLS  (fig. 21)

Warning:

 all installation operations must be performed with the system 

disconnected from the power supply; if fitted, the PR1 backup battery 
must also be disconnected.

Warnings: 

Take care not to damage the o-ring fitted (

fig. 21-3

[A]

.

Observe the following directions when selecting the installation position 
of the two elements that make up the photocell (TX and RX):
• Place them at a height of 40-60 cm from the ground, on both sides 

of the area to be protected and as flush with the gate as possible (the 
offset must not exceed 15 cm.).

•  The point of installation must be provided with a conduit for the wires.
• Point the TX transmitter at the RX receiver, with a maximum misalign-

ment of 5°.

01.

  Remove the front glass panel (

fig. 21-1

).

02.

  Position the photocell at the point where the cable routing tube 

arrives.

03.

  Trace the drilling points using the base as a reference. Drill the holes 

in the wall using a hammer drill fitted with a 5mm bit and insert the 5 
mm anchors in the wall.

04.

  Route the electric cables through the specific holes (pierce those 

required): see 

fig. fig. 21-2

.

05.

  Fix the base, using the related screws 

[B]

 in 

fig. 21-3

 ensuring that 

the hole on the base 

[C]

 in 

fig. 21-3

 is aligned with the cable outlet. 

Also 2 self-tapping screws are provided for fixing to surfaces with 
different densities.

06.

  Connect the electrical cable in the related terminals of both TX and 

RX (

fig. 21-4

). Connect the electrical cable in the relative terminals 

of both TX and RX (

fig. 21-5

) and to the blue terminal on the control 

board. No polarity needs to be observed.

07.

  Fix the covering shell 

[D]

 in 

fig. 21-6

 with the two screws 

[E]

 in 

fig. 

21-6

 using a Phillips screwdriver. Lastly, insert the external cover 

[F]

 

in 

fig. 21-6

 pressing it slightly to secure in place.

6.2 -  INSTALLING AND CONNECTING THE FLASHING  

LIGHT FL100 (fig. 20)

Select the position of the flashing light so that it is in the vicinity of the 
gate in a visible location. It can be fixed on either a horizontal or vertical 
surface. 

Fig. 22

 shows the two options:

01.

  Remove the cover, unscrewing the screw if present;

02.

  Separate the base, unscrewing the screws present to route the 

electric cables;

03.

  Trace the drilling holes using the base as a reference and ensuring 

that the hole on the base is aligned with the cable outlet: vertical fix-
ing (

A

) or horizontal fixing (

B

);

04.

  Use a percussion drill to drill the wall, with a 6 mm tip, and insert 6 

mm plugs;

05.

  Fix the base, using the related screws;

06.

  Connect the electric cables in the relative FLASH and “aerial” terminals 

as shown in the figure: The terminals can be removed in order to facili-
tate the operations; make the connections and then reinsert them.

 

You do not need to observe any polarity on the FLASH terminal; 
however, for the connection of the shielded cable to the aerial, con-
nect the sheath;

07.

  Insert the lamp holder in the base, taking care to press it down so 

that it locks into place;

08.

  Secure the body of the flashing light to the fixing support and turn it 

left until it clicks into place, then secure by means of the screw.

1 2

3

4

5

21

6

B

C

A

D

E

F

Содержание MhouseKit WS2S

Страница 1: ...MhouseKit WS2S For power operated swing gate Installation instructions and warnings and operating manual IS0004A01EN_07 02 2012...

Страница 2: ......

Страница 3: ...12 7 2 INITIAL CHECKS 12 7 3 RECOGNITION OF CONNECTED DEVICES 12 7 4 RECOGNITION OF THE GATE LEAF OPENING AND CLOSING ANGLES 12 7 5 CHECKING THE RADIO TRANSMITTERS 12 7 6 SETTINGS 12 TESTING AND COMM...

Страница 4: ...ed conformity of the automation In consideration of this all mains connection testing commissioning and mainte nance operations must be performed exclusively by a qualified and skilled technician All...

Страница 5: ...Tx and Rx Ensure that all devices to be installed are in a sheltered location and protected against the risk of accidental impact 3 2 PRODUCT APPLICATION LIMIT Before proceeding with installation perf...

Страница 6: ...position of all connection cables Refer to the instructions in paragraph 4 2 to establish the layout of the raceways for electric cable ducting 4 1 3 Ensure all equipment and materials for work are av...

Страница 7: ...5 D G B C D D E F a d g d e f b b c 1 3 4 5 A B E H F I 2 L G D C A...

Страница 8: ...ed to the leaf material 12 Turn the leaf to the required gate open position Place the limit switch against the straight arm L and tighten the two screws M fig 15 13 Loosen screw N securing the straigh...

Страница 9: ...7 8 10 NO 11 E D C 12 13 9 A B F G...

Страница 10: ...8 M L 15 17 N O P 16 Blue Yellow Green Brown 18 19 I 14 H H...

Страница 11: ...9 OPEN STOP TX TR ECS M M FLASH STOP OPEN M M bus ECS bus ECS FLASH bus M M M M WS1SCM2 WS1SK M1 KS100 PH100 FL100 Blue Yellow Green Brown B A 20...

Страница 12: ...electrical cable in the relative terminals of both TX and RX fig 21 5 and to the blue terminal on the control board No polarity needs to be observed 07 Fix the covering shell D in fig 21 6 with the t...

Страница 13: ...11 22 A B 6 mm x4 6 mm x4 A B A B A B A A A A B B B 1 2 3 4 4 A B A B A B A B A B A B 5 6 7 8 9 11 12 10 A B A B...

Страница 14: ...urred see paragraph 10 5 Troubleshooting The connected devices recognition stage can be repeated again at any time even after the installation for example if an additional photocell is installed just...

Страница 15: ...ablish what tests should be conducted based on the risks involved and verify the compliance of the system with applicable regulations legis lation and standards in particular with all the provisions o...

Страница 16: ...am e g fig 5 risk assessment and solutions adopted manufacturer s declaration of conformity for all devices used use appendix 1 EC declaration of conformity for components of WS2S 02 Affix a dataplate...

Страница 17: ...six times Press T2 seven times Press T2 eight times Press T3 once Press T3 twice Press T3 three times Press T3 four times Press T3 five times Press T3 six times Press T3 seven times Press T3 eight ti...

Страница 18: ...ly be made after completing all installation and pro gramming phases as the battery constitutes an emergency power supply To install and connect the buffer battery PR1 to the control unit refer to fig...

Страница 19: ...te the energy consumed by the automation proceed as follows 05 On the table below select the box corresponding to the intersection between the line with the weight and the column with the opening angl...

Страница 20: ...cognition of other devices Normally the recognition of the devices connected to the ECSBus and the STOP input takes place during the installation stage However if new devices are added or old ones rem...

Страница 21: ...to memorise it If the memorisation procedure is successful the P1 LED will flash 3 times 03 If there are other transmitters to be memorised repeat step 2 within the next 10 s otherwise the memorisati...

Страница 22: ...press any key on the two transmitters If on the other hand the OLD transmitter was memorised in Mode 2 you must press the key on the OLD transmitter which corresponds to the desired command and the k...

Страница 23: ...tent the voltage value is not important approximately 10 30 VAC if there is voltage the problem is due to the lamp in this case replace the lamp with one having the same characteristics TABLE 10 fig...

Страница 24: ...rmal operation and on possible faults see Table 13 Quick flashes 1 flash 1 second pause 1 flash 2 flashes 1 second pause 2 flashes 3 flashes 1 second pause 3 flashes 4 flashes 1 second pause 4 flashes...

Страница 25: ...e is under way Action Cyclic operation Complete cyclic operation Perform the recognition phase see chapter 3 5 2 Recognition of leaf opening and closing angles Opening angle recognition phase is under...

Страница 26: ...osing of the contact causes the OPEN command STOP input For normally open contacts and or for 8 2K constant resistance type contacts or normally closed contacts with recognition of the normal status a...

Страница 27: ...1 6 m s approx 20 approx 20 Up to 10m for maximum TX RX misalignment of 5 the device can signal an obstacle even in the case of adverse weather conditions The device can be connected only to ECSBus n...

Страница 28: ...d doors AM OOK coded modulation of radio carrier 433 92 MHz Rolling code with 64 Bit code 18 billion billion combinations 4 each key can be used for the different controls of the same control unit or...

Страница 29: ...WS1SC WS1SK PH100 and FL100 conform to DIRECTIVE 2004 108 CE 108 EC OF THE EUROPEAN PARLIA MENT AND COUNCIL of 15th December 2004 regarding the approximation of member state legislation related to el...

Страница 30: ...28...

Страница 31: ...and made available to all users of the automation 11 1 Safety instructions Keep an eye on the moving door and keep at a safe dis tance until the door has completely opened or closed do not cross the...

Страница 32: ...uch that a fault or an incorrectly balanced door could cause injury 11 5 Remote control battery replacement fig 43 When the battery charge is low the range of the transmitter is significantly reduced...

Страница 33: ...ation address Complies with the essential requirements of the following directives 2006 42 EC Machinery Directive 2004 108 EEC Electromagnetic Compatibility Directive 2006 95 EEC Low Voltage Directive...

Страница 34: ......

Страница 35: ......

Страница 36: ...Mhouse is a commercial trademark owned by Nice S p a Nice S p a Via Pezza Alta 13 Z I Rustign 31046 Oderzo TV Italy Tel 39 0422 85 38 38 Fax 39 0422 85 35 85...

Отзывы: