© MHG Heating Ltd
MHG Heating Ltd, Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey, KT20 5LR
P:0845 6448802 F:0845 6448803 E:
W: www.mhgheating.co.uk
010617
61
N.
Low Fire Adjuster (Governor Type)
Each module must be analysed and adjusted separately.
This is undertaken by inserting the analysers probe in to the silicone sampling tube
secured to the top of each module and sealed with a black plug. If fluctuating
figures are obtained the flue gas analyser should be inserted directly into the module
flue spigot once the silicone tube has been temporally removed.
(Taking care not to dislodge the
grommet)
Each module must be set to the following combustion figures.
Gas Type
Injector Size
High Fire
Low Fire
Natural Gas (G20)
15mm
(Exploded Part #79)
8.5% C0
2
9.0% CO
2
LPG (G31)
10mm
(Exploded Part #79)
11.0% CO
2
11.0% CO
2