36
820
Pump heating circuit overtemp
protection HC1
On
830
Mixing valve setpoint boost heating
circuit 1
5
°C
832
Actuator control mode heat circuit 1
Three-position
833
Actuator switching differential heat
circuit 1
2
°C
834
Actuator running time heat circuit 1
120
s
835
P-band (Xp) heat circuit 1
32
°C
836
Integral action time (Tn) heat circuit 1
120
s
850
Flooring plaster dry up function HC1
Off
851
Floor setpoint manually HC1
25
°C
861
Overtemperaturedrop heating circuit 1
Always
870
Heating circuit 1 with buffer
Yes
872
Heating circuit 1 with
precontr/primary pump
Yes
900
Operating mode changeover heating
circuit 1
Protection
Cooling circuit 1
901
Operating mode cooling circuit 1
Automatic
902
Room temp Comfort setpoint cooling
circuit 1
24
°C
907
Release cooling circuit 1
24h/day
908
Flow setpoint at outside temp 25°C
CC1
20
°C
909
Flow setpoint at outside temp 35°C
CC1
16
°C
912
Cooling limit at outs temp cooling
circuit 1
20
°C
913
Remaining time after heating cooling
circuit 1
24
h
918
Start summer compensation at ouside
temp CC1
26
°C
919
End summer compensation at ouside
temp CC1
35
°C
920
Summer compensation setpoint
increase CC1
4
°C
923
Flow setpoint min at outside temp
25°C CC1
18
°C
924
Flow setpoint min at outside temp
35°C CC1
18
°C
928
Room temperature gain factor cooling
circuit 1
80
%
932
Room temp limitation cooling circuit 1
0.5
°C
938
Mixing valve decrease cooling circuit
1
0
°C