Actuator control mode cooling circuit
1
Three-position
940
Actuator switching diff cooling circuit
1
2
°C
941
Running time actuator cooling circuit
1
120
s
942
P-band (Xp) cooling circuit 1
12
°C
943
Integral action time (Tn) cooling
circuit 1
90
s
945
Mixing valve cooling circuit 1 in
heating mode
Controlled
946
Locking time dew point limit CC1
60
min
947
Flow boost hygrostat cooling circuit 1
10
°C
948
Flow setpincr start at rel Humidity
CC1
60
%
950
Flow temp diff dewpoint
2
°C
962
Cooling circuit 1 with buffer
No
963
Cooling circuit 1 with
precontr/primary pump
No
969
Operating mode changeover cooling
circuit 1
Off
Heat circuit 2
1000
Operating mode heat circuit 2
Automatic
1010
Room temperature Comfort setpoint
HC2
20
°C
1012
Room temp reduced setpoint heat
circuit 2
16
°C
1014
Room temp frost protection setpoint
HC2
10
°C
1016
Comfort setpoint max HC2
35
°C
1020
Heating curve 2 slope
3.2
1021
Heating curve parallel displacement
HC2
0
°C
1026
Heating curve adaptation heat circuit
2
Off
1030
Summer/winter changeover temp heat
circuit 2
18
°C
1032
24-hour heating limit HC2
-3
°C
1040
Flow temp min limitation heat circuit
2
8
°C
Set to required
minimum flow
temperature
1041
Flow temp max limitation heat circuit
2
80
°C
Set to required
maximum heating
flow temperature
1050
Room temp gain factor heat circuit 2
20
%
1060
Room temperature limitation heating
circuit 2
1
°C