Boiler
2200
Boiler operating mode
Automatic mode
without boiler
run time
extension
2203
Release oil-/gas boil below outside
temp thresh
-------
°C
2205
Boiler with economy mode
Off
2208
Full charging buffer
Off
2210
Boiler temp min limitation
8
°C
2211
Boiler temp min limitation OEM
8
°C
2212
Boiler temp max limitation
90
°C
2213
Boiler temp max limitation OEM
95
°C
2240
Boiler switching differential
8
°C
2241
Burner running time min limitation
4
min
2250
Pump overrun time
5
min
2260
Protective start up consumer
On
2261
Protective start up boiler pump
On
2262
Optimum start control min limitation
boiler temp
Off
2270
Return temp limitation
8
°C
2271
Min. limitation of the boiler return
temp EXP
8
°C
2272
Boiler return flow
On
2282
Actuator running time return temp
limitation
120
s
2283
P-band (Xp) return temp limitation
32
°C
2284
Integral action time (Tn) return temp
limitation
120
s
2285
Derivative action time (Tv) return
temp limit
10
s
2290
Bypass pump switching differential
6
°C
2291
Bypass pump control
According to
boiler return
temp
2300
Frost protection for plant boiler
pump
Off
2310
TR function
On
2315
Temperature stroke min
-------
°C
2316
Temperature stroke max
-------
°C
2330
Nominal power boiler
50
kW
2331
Nominal power first stage
30
kW
Cascade
3510
Cascade control strategy
Early on, late off