35
662
Holiday period 6 HC3/P: First day
-------
663
Holiday period 6 HC3/P: Last day
-------
662
Holiday period 7 HC3/P: First day
-------
663
Holiday period 7 HC3/P: Last day
-------
662
Holiday period 8 HC3/P: First day
-------
663
Holiday period 8 HC3/P: Last day
-------
668
Holiday operating level HC3/P
Frost
Heat circuit 1
700
Operating mode heat circuit 1
Protection
710
Room temperature Comfort setpoint
HC1
21
°C
712
Room temp reduced setpoint heat
circuit 1
16
°C
714
Room temp frost protection setpoint
HC1
10
°C
716
Comfort setpoint max heating circuit
1
35
°C
720
Heating curve 1 slope
3.2
721
Heating curve parallel displacement
HC1
0
°C
726
Heating curve adaptation heat circuit
1
Off
730
Summer/winter changeover temp heat
circuit 1
18
°C
732
24-hour heating limit HC1
-3
°C
740
Flow temp min limitation heat circuit
1
8
°C
Set to required
minimum flow
temperature
741
Flow temp max limitation heat circuit
1
80
°C
Set to required
maximum heating
flow temperature
750
Room temp gain factor heat circuit 1
20
%
760
Room temperature limitation heating
circuit 1
1
°C
770
Room temp setpoint boost HC1 (boost
heating)
5
°C
780
Quick setback heat circuit 1
Down to reduced
setp
790
Optimum start control max forward
shift HC1
00:00
h:m
791
Optimum stop control max forward
shift HC1
00:00
h:m
800
Start reduced room temp setpoint
increase HC1
-------
°C
801
End reduced room temp setpoint
increase HC1
-15
°C