43
3832
Collector Start function on
07:00
h:m
3833
Collector Start function off
19:00
h:m
3834
Collector Start function gradient
-------
min/°C
3840
Collector frost protection temp
-------
°C
3850
Collector over temperature protection
-------
°C
3860
Evaporation temperature of heat
carrier
-------
°C
3880
Type of antifreeze added
None (water)
3881
Antifreeze concentration
30
%
3884
Volumetric flow solar pump
200
l/h
Solid fuel boiler
4102
Solid fuel boiler locks other producers
On
4110
Min solid fuel boiler setpoint
40
°C
4130
Temp differential on solid fuel boiler
8
°C
4131
Temp differential off solid fuel boiler
4
°C
4133
Comparative temperature solid fuel
boiler
Setpoint min
4140
Pump overrun time solid fuel boiler
20
min
4141
Over temperature drop solid fuel
boiler
90
°C
4170
Frost protection for plant solid fuel
boiler
Off
Buffer tank
4720
Automatic producer lock
With B4
4721
Automatic producer lock switching
differential
8
°C
4722
Diff. Buffer/HC temp to producer
release
-5
°C
4723
Temp diff buffer/CC to source release
0
°C
4724
Min buffer temp while heating mode
-------
°C
4726
Max buffer temp while cooling mode
25
°C
4739
Buffer stratification protection
Off
4740
Buffer stratification protect Temp diff
max
5
°C
4743
Buffer stratification protect
foreseeable time
60
s
4744
Buffer stratification prot integral
action time
120
s
4746
DHW protection combi storage
Off
4750
Buffer charging temp max
80
°C
4751
Buffer temp max
90
°C
4755
Return cooling temperature buffer
60
°C
4756
Buffer return cooling DHW/HC
Off
4757
Buffer return cooling Collector
Off
4783
Buffer with solar
No
4790
Return diverting temp differential On
10
°C
4791
Return diverting temp differential Off
5
°C