5.0 Technical Data
Technical Data
150 (150 Plate X)
225 (225 Plate X)
Nominal Heat Input Net
Min/Max
kW
15.0/149.2
15.0/216.0
Nominal Heat Output
(50ºC/30ºC)
Min/Max
kW
16.0/155.0
16.0/225.0
Nominal Heat Output
(80ºC/60ºC)
Min/Max
kW
14.5/143.2
14.5/206.0
Operating Efficiency (40ºC/30ºC)
%
109.5
109.5
Design Water Flow Rate
Ltr/sec
1.8
2.66
Residual Head from In-built Pumps
(Cascade version only)
kPa
15.0 (0)
15.0 (0)
Maximum Input Gas Rate
G20
G31
m³/hr
m³/hr
15.0
5.77
21.7
8.35
Gas Inlet Pressure
Min/Max
mbar
18.0/50.0
18.0/50.0
Maximum Flue Gas Mass
G20 (Hot)
Kg/hr
250.9
363.6
Maximum Flue Gas Mass
G31 (Hot)
Kg/hr
231.4
335.1
Residual Fan Pressure
Pa
200
200
Maximum Water Pressure
(Hot)
bar
3.0 (System 10)
3.0 (System 10)
Minimum Water Pressure
(Cold)
bar
1.0 (System 1)
1.0 (System 1)
Maximum Flow Temperature
ºC
90 (85)
90 (85)
Power Supply (240 V /50 Hz)
Amps
7
7
Max Power Consumption
Watts
690
800
Water Content
Ltrs
30
35
Lift Weight (Dry)
kg
250
270
Lift Weight (Wet)
kg
280
305
Efficiency @ Full Load Gross
%
86.48
85.67
Efficiency @ 30% of Full Load Gross
%
98.20
98.37
NOx emission @ 0% O
2
Mg/kWh
26.7 (Class 5)
Flue Classification
B23, C33, C43, C53, C63, C83.