39
1340
Flow temperature min limitation
HC3/P
8
°C
1341
Flow temperature max limitation
HC3/P
80
°C
1350
Room temperature authority HC3/P
20
%
1360
Room temperature limitation HC3/P
1
°C
1370
Room setpoint boost HC3/P (boost
heating)
5
°C
1380
Quick setback HC3/P
Down to reduced
setp
1390
Optimum start control max forward
shift HC3/P
00:00
h:m
1391
Optimum stop control max forward
shift HC3/P
00:00
h:m
1400
Start reduced room temp setpoint
increase HC3/P
-------
°C
1401
End reduced room temp setpoint
increase HC3/P
-15
°C
1420
Pump heating circuit overtemp
protection HC3/P
On
1450
Floor curing function HC3/P
Off
1451
Floor setpoint manually HC3/P
25
°C
1455
Flow temperature setpoint floor
curing HC3/P
-------
°C
1456
Floor curing day HC3/P
-------
1457
Floor curing HC3/P days fulfilled
0
1461
Over temperature drop heating circuit
3/P
Always
1470
Heating circuit 3/P with buffer
Yes
1472
Heating circuit 3/P with pre
contr/primary pump
Yes
1500
Operating mode changeover HC3/P
Protection
DHW
1600
DHW operating mode
On
1610
DHW temperature nominal setpoint
55
°C
1612
DHW temperature reduced setpoint
40
°C
1614
DHW temperature nominal setpoint
max
65
°C
1620
DHW release
Heating
programs with
forward shift
1630
DHW charging priority
Shifting,
absolute
1640
Legionella function
Fixed weekday
1641
Legionella function periodicity
3
1642
Legionella function day
Monday
1644
Time for legionella function
-------
h:m