INSTALLATION AND WIRING
2.2 Wiring
2.2.1
Terminal connection diagram
3-phase 575V power input
Note:1. If the potentiometer is to be operated often, use a 2W1k
Ω
potentiometer.
2. Terminals SD and SE are isolated.
3. Terminals SD and 5 are common terminals. Do not ground them to the ground.
4. When terminals PC-SD are used as a 24VDC power supply, be careful not
to short these terminals. If they are shorted, the inverter will be damaged.
3-phase AC
power supply
MCCB
STF
STR
RH
RM
RL
MRS
RES
Forward rotation start
Middle
High
Low
Output stop
Reset
Frequency setting signals (Analog)
10(+5V)
2
2
3
1
4 to )
4(4 to 20mADC)
1/2W1k
Ω
RUN
FU
SE
Running
Frequency detection
Jumper
Remove this jumper when
using the optional power-factor
improving DC reactor.
Brake resistor connection
Motor
IM
Alarm
output
A
B
C
U
V
W
P1
PR
0 to 5VDC
0 to 10VDC
Selected
Multi-speed selection
5
(Note 1)
Frequency
setting
potentiometer
Current input(-)
Reverse rotation start
MC
Main circuit terminal
Control circuit input terminal
Control circuit output terminal
When using current input as the
frequency setting signal, set "4" in
any of Pr.180 to Pr.183 (input
terminal function selection) and
assign AU (current input selection)
to any of terminal RH, RM, RL, or
MRS, then turn the AU signal on.
(
-
)
AM
5
(+) Analog signal
output
(0 to 10VDC)
Ground
PU connector
(RS-485)
Contact input common
Control input signals
(No voltage input allowed)
SD
Note 3
SD
Note 2
PC
24VDC power output and
external transistor common
Note 4
R(L
1
)
S(L
2
)
T(L
3
)
(+)P
(-)N
Note 3
Ground
Ground
Note 2
(Common)
Open collector output common
Sink/source common
Open
collector outputs