17
2
INSTALLATION AND WIRING
(1) Description of the main circuit terminals
Symbol
Terminal Name
Description
R, S, T
(L
1
, L
2
, L
3
)
AC power input
Connect to the commercial power supply.
U, V, W
Inverter output
Connect a three-phase squirrel-cage motor.
P (+), PR
Brake resistor
connection
Connect the optional brake resistor across terminals P-
PR (+ - PR).
P (+), N (-)
Brake unit
connection
Connect the optional brake unit.
P (+), P1
Power factor
improving
DC reactor
connection
Disconnect the jumper from terminals P-P1 (+ - P1) and
connect the optional power factor improving DC reactor.
Ground
For grounding the inverter chassis. Must be grounded.