108
PARAMETERS
4.2.30 Reset selection/disconnected PU detection/PU stop
selection (Pr. 75)
Pr. 75 "reset selection/disconnected PU detection/PU stop selection"
You can select the reset input acceptance, PU(FR-PA02
-02
/FR-PU04-MGI) connector
disconnection detection function and PU stop function.
• Reset selection
: You can select the reset function input timing.
• PU disconnection detection: When it is detected that the PU(FR-PA02
-02
/FR-PU04-
MGI) is disconnected from the inverter for more than 1s,
the inverter outputs an alarm code (E.PUE) and comes
to an alarm stop.
• PU stop selection
: When an alarm occurs in any operation mode, you can
stop the inverter from the PU by pressing the
key.
<Setting>
Parameter
Number
Factory
Setting
Setting Range
75
14
0 to 3, 14 to 17
Pr. 75
Setting
Reset Selection
PU Disconnection
Detection
PU Stop
Selection
0
Reset input normally enabled.
If the PU is disconnected,
operation will be continued.
Pressing the
key
decelerates the
inverter to a stop
only in the PU
operation mode.
1
Reset input enabled only when the
protective function is activated.
2
Reset input normally enabled.
When the PU is
disconnected, an error is
displayed on the PU and the
inverter output is shut off.
3
Reset input enabled only when the
protective function is activated.
14
Reset input normally enabled.
If the PU is disconnected,
operation will be continued.
Pressing the
key
decelerates the
inverter to a stop
in any of the PU,
external and
communication
operation
modes.
15
Reset input enabled only when the
protective function is activated.
16
Reset input normally enabled.
When the PU is
disconnected, an error is
displayed on the PU and the
inverter output is shut off.
17
Reset input enabled only when the
protective function is activated.
STOP
RESET
STOP
RESET
STOP
RESET