95
4
PARAMETERS
4.2.22 Automatic restart after instantaneous power failure
(Pr. 57, Pr. 58)
Pr. 57 "restart coasting time"
Pr. 58 "restart cushion time"
•
You can restart the inverter without stopping the motor (with the motor coasting) when
power is restored after an instantaneous power failure.
<Setting>
Refer to the following table and set the parameters:
*The output shut off timing differs according to the load condition.
Parameter
Number
Factory
Setting
Setting Range
Remarks
57
9999
0 to 5 s, 9999
9999: No restart
58
1.0 s
0 to 60 s
Parameter
Number
Setting
Description
57
0
001 to 002
0.5 s coasting time
Generally use this
setting.
003 to 010
3.0 s coasting time
0.1 to 5 s
Waiting time for inverter-triggered restart after power is restored
from an instantaneous power failure. (Set this time between 0.1s
and 5s according to the inertia moment (J) and torque of the load.)
9999
No restart
58
0 to 60 s
Normally the inverter may be run with the factory settings. These
values are adjustable to the load (inertia moment, torque).
Pr. 58 setting
Instantaneous power
failure (power failure) time
Power supply
STF(STR)
Motor speed
(r/min)
Inverter output
frequency
(Hz)
Inverter output
voltage
(V)
Coasting time
Pr. 57 setting
Restart
voltage
cushion time
(R, S, T)
*
M4500E.book 95 ページ 2005年2月22日 火曜日 午後5時7分