143
4
PARAMETERS
4.2.38 Output current detection function (Pr. 150, Pr. 151)
Pr. 150 "output current detection level"
Pr. 151 "output current detection period"
•
If the output current remains higher than the Pr. 150 setting during inverter operation
for longer than the time set in Pr. 151, the output current detection signal (Y12) is
output from the inverter's open collector output terminal.
(Use any of Pr. 190 to Pr. 192 to assign the terminal used for Y12 signal output.)
<Setting>
Refer to the following list and set the parameters:
Parameter
Number
Factory
Setting
Setting
Range
150
150%
0 to 200.0%
151
0s
0 to 10 s
Parameter
Number
Description
150
Set the output current detection level.
100% is the rated inverter current.
151
Set the output current detection time. Set a period of time from when the
output current rises to or above the Pr. 150 setting to when the output current
detection signal (Y12) is output.
Note:1. Once turned ON, when the output current has risen above the preset
detection level, the output current detection signal is held for at least 100ms
(approximately).
2. This function is also valid during execution of offline auto tuning.
3. When the terminal functions are changed using Pr. 190 to Pr. 192, the other
functions may be affected. Confirm the functions of the corresponding
terminals before making settings.
Pr. 190 to Pr. 192
(output terminal function
selection)
Related parameters
Time
OFF
ON
OFF
100ms
Pr.151
Pr.150
O
ut
put
c
ur
rent
Output current
detection signal (Y12)
M4500E.book 143 ページ 2005年2月22日 火曜日 午後5時7分