15 Appendix
11-3
Homing: timeout
The maximum permissible time for the homing
run has been reached before the homing run
could be completed.
Check the time value
11-4
Homing: incorrect /
invalid limit switch
Has the associated limit switch not been
connected?
Have the limit switches been mixed up?
11-5
Homing: I²t / following
error
Unsuitable parameterisation of the acceleration
ramps.
The stop has been reached, e.g. because no
reference switch has been installed.
11-6
Homing: end of search
distance reached
The maximum distance for the homing run has
been covered, but the reference point or the
target of the homing run have not been reached.
11-7
Homing: encoder
difference monitoring
The deviation fluctuates, e.g. due to gear
slackness. If necessary, increase the switch-off
threshold.
Check the connection of the actual value
encoder.
Group 12: CAN communication
12-0
CAN: duplicate node
number
Check the configuration of the devices that are
connected to the CAN bus.
12-1
CAN: communication
error, bus OFF
Check the wiring: compliance with the cable
specification, cable break, maximum cable
length exceeded, correct terminating resistors,
cable shield earthed, all signals connected?
12-2
CAN: communication
error (sending)
12-3
CAN: communication
error (receiving)
12-4
CAN: Node Guarding
Failure of the PLC or the cycle time of the remote
frames of the servo drive and PLC do not match.
12-5
CAN: RPDO too short
The number of bytes of a received RPDO is
smaller than the number that is parameterised in
the servo drive.
12-9
CAN: protocol error
Please contact the Technical Support team.
Group 13: Timeout CAN bus
13-0
Timeout CAN bus
Check the CAN parameterisation.
Group 14: Motor and resolver identification
14-0
Insufficient DC bus
circuit voltage
Check the power supply voltage.
Check the motor resistance.
14-1
Identification current
controller: measuring
cycle insufficient
The automatic parameter identification process
delivers a time constant beyond the value range
that can be parameterised. The parameters must
be optimised manually.
14-2
Power output stage
could not be enabled
The power output stage has not been enabled.
Check the connection of DIN4.
14-3
Power output stage
prematurely disabled
The power stage has been disabled while the
identification process was still running (for
example via DIN 4 or via PLC).
Product manual BL 4000-C
Page 272 of 298
Содержание smartServo BL 4000-C Series
Страница 1: ...Important Read thoroughly before use Retain for future reference Product manual smartServo BL 4000 C ...
Страница 261: ...15 Appendix 15 2 CE conformity in accordance with the Machinery Directive Product manual BL 4000 C Page 261 of 298 ...
Страница 262: ...15 Appendix Product manual BL 4000 C Page 262 of 298 ...
Страница 263: ...15 Appendix 15 3 cULus certification Product manual BL 4000 C Page 263 of 298 ...