Installation and 

operating manual

SHK 200S 
SHK 200S-6

Indoor unit Cooperating with 
air heat pumps

EKSPERTER I VARME OG VARMT VAND

30147

Содержание SHK 200S

Страница 1: ...Installation and operating manual SHK 200S SHK 200S 6 Indoor unit Cooperating with air heat pumps EKSPERTER I VARME OG VARMT VAND 30147...

Страница 2: ......

Страница 3: ..._________________________________26 Settings__________________________________________27 7 Start up and regulation___________28 Preparations______________________________________28 Filling and venting...

Страница 4: ...ilities and without any experience or knowledge about its operation if supervised or trained in safe opera tion and if they understand the risks related to its operation The device must not serve as a...

Страница 5: ...odule Building fuses Temperature sensor outdoor Room sensor Energy meter Emergency switch Switch differential Thermostat emergency mode setting Miscellaneous Connected to Installation acceptance The h...

Страница 6: ...S SHK 200S 6 is equipped with condensate drain indoor unit installation site must be furnished with a fl oor drain with a dis charge to the sewer system 1 Remove screws at the bottom edge of the front...

Страница 7: ...ter 3 Indoor module structure SHK 200S SHK 200S 6 XL11 XL10 XL4 XL13 XL14 XL3 AA27 AA8 AA2 X4 AA2 X15 AA2 K2 XL2 XL1 BT6 BT7 X0 BT30 X1 FD1 EB1 FA2 FA1 K1A K3A AA23 AA3 X2 AA7 EB2 SF1 GP12 BT64 EP2 QN...

Страница 8: ...ture sensor condenser outlet BT15 Temperature sensor liquid BT25 Temperature sensor heating medium supply BT63 Temperature sensor heating medium sup ply downstream the submersible heater BT64 Temperat...

Страница 9: ...ystems need to be flushed out before the indoor module is connected so that any debris cannot damage component parts IMPORTANT As long as heating circuits in the system have not been filled with the h...

Страница 10: ...low temperatures up to 20 C The connection of the outdoor unit and indoor unit SHK 200S SHK 200S 6 with a system of pipes filled with a cooling medium secures the connection against freezing in the e...

Страница 11: ...that they are not adjacent to the bedroom or living room Remember to leave about 800 mm free space at the front and 220 mm over the device to provide for future maintenance 1 Connect SHK 200S SHK 200...

Страница 12: ...2 mm manometer XL13 Liquid cooling medium Connection SHK 200S 6 Connection SHK 200S XL14 Gas cooling medium Connection SHK 200S 6 Connection SHK 200S XL 18 Connection return to an additional heat sour...

Страница 13: ...all heaters have been equipped with thermostat valves install a discharge valve or remove sever al thermostats to assure appropriate flow Symbol Application L6 SHK 200S 6 L8 SHK 200S L12 IMPORTANT Th...

Страница 14: ...R L mode where pipes are to be led The drawing below presents exem plary pipe outlets Make sure that no water or dirt can permeate to the pipes Contamination of the pipes may damage the heat pump A B...

Страница 15: ...order to achieve a better final effect and to acceler ate emptying follow the following sections Pipelines should have the largest diameter possi ble and be as short as possible Empty the system to 4...

Страница 16: ...200S SHK 200S 6 65 C Max flow line temperature with compressor 58 C Min supply temperature cooling 7 C Max supply temp cooling 25 C Min volume climate system during heating cooling 50 l 80 l 100 l Mi...

Страница 17: ...connection The system can be extended with additional heating cir cuits only when provided an additional expansion card After using anAXC30 card or a ECS 41 kit an additional heating circuit can be ac...

Страница 18: ...ve the plug from the circulation pipe XL5 4 Install the elbow facing the rear housing on the circulation pipe 5 Connect the pipe to the elbow with the dimen sions shown in the figure below leading pip...

Страница 19: ...con crete foundation If concrete slabs are used they must rest on asphalt or shingle The concrete foundation or slabs must be posi tioned so that the lower edge of the evaporator is at the level of th...

Страница 20: ...st free or alternatively in doors with reservation for local ordinances and regulations Use a water trap for installations where air circu lation may occur in the condensation water pipe The insulatio...

Страница 21: ...t free depth Route the pipe downward from the air water heat pump The condensation water pipe must have a water seal to prevent air circulation in the pipe The installation length can be adjusted by t...

Страница 22: ...METROAIR L8 METROAIR L6 30 30 188 25 750 24 61 340 48 51 12 150 223 310 580 61 150 32 880 88 418 380 19 49 104 Nad 43 93 640 40 40 12 148 34 89 51 44 290 84 510 327 201 18 800 12 71 352 313 5 1 4 2 C...

Страница 23: ...200S 6 METROAIR L12 388 190 60 580 200 262 38 40 50 370 410 20 40 60 15 60 20 970 50 55 15 845 10 50 110 195 242 279 50 27 50 52 195 110 100 40 51 36 50 150 70 15 50 40 103 15 Prawo Chapter 5 Outdoor...

Страница 24: ...the side that faces the least sound sensitive neighbouring area The sound pressure levels are further affected by walls bricks differences in ground level etc and should therefore only be seen as guid...

Страница 25: ...h the heating medium and if the central heating system has not been vented the switch SF1 in controller cannot be set in positions I or Otherwise the temperature limiter thermostat and flow through he...

Страница 26: ...nal contacts at the distances lower than 20 cm from high voltage cables Power supply connection Temperature limiter Temperature limiter FD1 cuts off the power supply of the electrical heating module i...

Страница 27: ...ntroller automation is in the emergency mode SF1 is set as only the most necessary functions are active Domestic hot water is not heated Constant temperature in the supply pipeline more information to...

Страница 28: ...wing for flow in all circuits 3 Open the valve for filling the heating installation and fill it with the heating medium 4 Close the vent when the heating medium flows out of it continuously without ai...

Страница 29: ...tallation s basic settings The start guide ensures that start up is carried out correctly and cannot be bypassed The start guide can be started later in menu 5 7 During the start up guide the reversin...

Страница 30: ...her consult the help menu or read the user manual C Option setting Make settings for the system here D Help menu In many menus there is a symbol that indicates that extra help is available To access t...

Страница 31: ...ump switches off and the immersion heater engages The control module display is not illuminated and the status lamp illuminates yellow The status lamp indicates the status of the con trol module It li...

Страница 32: ...in the start menu See page 49 Symbol Description This symbol appears by the infor mation sign if there is information in menu 3 1 that you should note These two symbols indicate whether the compresso...

Страница 33: ...finished writing mark OK and press the OK button 1 Turn the control knob until one of the arrows in the top left corner at the page number has been marked 2 Press the OK button to skip between the st...

Страница 34: ...g 1 3 3 ventilation 1 1 9 advanced 1 9 1 curve 1 9 1 1 heating curve 1 9 1 2 cooling curve 1 9 2 external adjustment 1 9 3 min flow line temp 1 9 3 1 heating 1 9 3 2 cooling 1 9 4 room sensor settings...

Страница 35: ...temporary lux 2 2 comfort mode 2 3 scheduling 2 9 advanced 2 9 1 periodic increase 2 9 2 hot water recirc 2 3 INFO 3 1 service info 3 2 compressor info 3 3 add heat info 3 4 alarm log 3 5 indoor temp...

Страница 36: ...tariffperiods electricity 4 1 8 6 tariffper ext shuntadd 4 1 8 7 tariffper ext stepadd 4 1 8 8 tariff periods 4 1 10 solar electricity 5 4 2 op mode 4 3 my icons 4 4 time date 4 6 language 4 7 holiday...

Страница 37: ...13511 5 3 15 GBM communicationsmodule12 5 3 16 humidity sensor 13 5 3 20 flow sensor 14 5 4 soft in outputs 5 5 factory setting service 5 6 forced control 5 7 start guide 5 8 quick start 5 9 floor dry...

Страница 38: ...ensor cooling inactive start active cooling 60 DM step difference compressors 30 DM degree minutes cooling 1 DM In this menu we have the possibility to check the al lowed values for external sensors M...

Страница 39: ...his menu it is possible to edit the minimum flow tem perature of the heating system More information after selecting Factory setting climate system 1 20 C In this menu it is possible to edit the maxim...

Страница 40: ...n after selecting Set the temperature without rooms ensors installed and activated Setting range 10 do 10 Factory setting 0 In this menu you can select the operating mode for the SHK 200S SHK 200S 6 u...

Страница 41: ...g curves for your house The task of the curve is to give an even indoor temper ature regardless of the outdoor temperature and thereby energy efficient operation It is from these heat curves that the...

Страница 42: ...o the climate system This means that SHK 200S SHK 200S 6 never calculates a temperature lower than that set here If there is more than one climate system the setting can be made separately for each sy...

Страница 43: ...t are running cooling In this menu user can create own heating or cooling curve by setting the desired supply temperatures for different outdoor temperatures You can use SHK 200S SHK 200S 6 to cool th...

Страница 44: ...duling Here you can program the hot water temperature for two different time intervals throughout the day Scheduling is activated deactivated by ticking untick ing activated Set times are not affected...

Страница 45: ...us information of the menu is displayed to the right of the menu Information about the heat pump s actual operating sta tus e g current temperatures etc can be obtained here No changes can be made The...

Страница 46: ...that is most car bon neutral at the time More information after select ing The heat pump operating mode is usually set to auto It is also possible to set the heat pump to add heat only but only when a...

Страница 47: ...rature Cooling ventilation and pool can also be scheduled if the functions are connected If a room sensor is installed and activated the desired room temperature C is set during the time period This s...

Страница 48: ...e and determine when the compressor respectively additional heat will start stop More information after selecting All settings that are available to the user including ad vanced menus can be reset to...

Страница 49: ...tings for the control module system settings System settings for the control module activating accessories etc accessory settings Operational settings for dif ferent accessories soft in outputs Settin...

Страница 50: ...ly add heat mode Max diff addi tional heat can never exceed max diff compressor stop temp per increase Setting range 55 70 C Factory setting 55 C step difference compressors Setting range 0 5 4 0 C Fa...

Страница 51: ...Factory setting binary stepping inactive Factory setting add type step controlled Factory setting positioning before QN10 normal and speed 1 4 Setting range 0 100 Factory setting normal 75 Factory set...

Страница 52: ...ll occur This menu can consist of several windows one for each available demand use the navigation arrows in the top left corner to change between the windows Menu 5 2 system settings Menu 5 2 2 insta...

Страница 53: ...menu 5 2 4 IMPORTANT Menu 5 3 3 is inactive in the factory settings For this menu function to be active the ECS accessory must be installed and activated in the accessories menu 5 2 4 IMPORTANT Menu...

Страница 54: ...nstructions for the individual accessories Menu 5 3 16 humidity sensor Menu 5 6 forced control Menu 5 7 start guide Menu 5 8 quick start You can force control the different components in the control m...

Страница 55: ...ompressor in the heat pump Factory setting This menu allows setting the rotations with which the GP10 circulating pump is to run in the current operat ing mode In auto mode the speed of the feed pump...

Страница 56: ...er is not produced The compressors are switched off Charge pump EB101 GP12 and charge pump EB102 GP12 if installed are running Accessories are switched off The heating medium pump is active The emerge...

Страница 57: ...of the display shows informa tion always in English of the most probable update that the update software has selected form the USB memory This information states which product the software is intended...

Страница 58: ...copy the settings to another controller Via recover settings you reset all menu settings from the USB memory Here you can choose how current measurement val ues from the controller should be saved on...

Страница 59: ...acing a hose in the cold water connection To facilitate the servicing of the heating system it must first be emptied using the filling valve IMPORTANT When emptying the side of the heating medium heat...

Страница 60: ...ing some kind of problem This can mean that the heat pump s compressor is not running In this case any electrical addition pro duces heat and or hot water If the operational interference is not shown...

Страница 61: ...rnal switches There is no heating requirement The controller does not call on heating or hot water Compressor blocked due to the temperature con ditions Wait until the temperature is within the prod u...

Страница 62: ...pe Cu 22 mm Max heat pump size 8 kW Part no 089 982 Reversing valve pipe Cu 22 mm Part no 067 311 Reversing valve Cu pipe Cu 28 mm Max recommended capacity 17 kW Part no 089 152 Reversing valve Cu pip...

Страница 63: ...63 SHK 200S SHK 200S 6 13 Technical data Dimensions and layout of connections 20 40 1600 115 Chapter 13 Technical data 600 5 610 5 300 156 93 5 92 5 87 63 55 65 155 44 152...

Страница 64: ...metres extra refrigerant must be added at a rate of 0 06 kg m Outdoor module Unit METROAIR L6 METROAIR L8 METROAIR L12 Starting current A 5 Compressor Twin Rotary Max fan flow heating nominal m3 h 2...

Страница 65: ...2 61 7 10 2 65 2 68 9 45 3 41 2 77 35 18 C 7 03 2 03 3 45 9 19 2 98 3 08 11 20 3 58 3 12 Max operating current and recommended fuse rating when connected 3x400 V Unit SHK 200S 6 L6 SHK 200S L8 SHK 20...

Страница 66: ...844 7 798 11 197 Annual energy consumption space heating warm climate kWh 872 1 398 1 879 2 333 2 759 3 419 Seasonal space heating energy efficiency cold climate 143 116 139 108 142 111 Seasonal space...

Страница 67: ...72 COPd Tj 7 C kW 1 8 Pdh Tj 7 C 6 47 COPd Tj 12 C kW 2 7 Pdh Tj 12 C 1 88 COPd Tj biv kW 4 7 Pdh Tj biv 1 77 COPd Tj TOL kW 4 1 Pdh Tj TOL COPd Tj 15 C if TOL 20 C kW Pdh Tj 15 C if TOL 20 C C 10 TO...

Страница 68: ...W 2 6 Pdh Tj 7 C 5 93 COPd Tj 12 C kW 3 7 Pdh Tj 12 C 1 83 COPd Tj biv kW 6 6 Pdh Tj biv 1 86 COPd Tj TOL kW 5 9 Pdh Tj TOL COPd Tj 15 C if TOL 20 C kW Pdh Tj 15 C if TOL 20 C C 10 TOL Min outdoor air...

Страница 69: ...kW 3 5 Pdh Tj 7 C 6 25 COPd Tj 12 C kW 5 0 Pdh Tj 12 C 1 90 COPd Tj biv kW 9 2 Pdh Tj biv 1 92 COPd Tj TOL kW 8 1 Pdh Tj TOL COPd Tj 15 C if TOL 20 C kW Pdh Tj 15 C if TOL 20 C C 10 TOL Min outdoor ai...

Страница 70: ...70 SHK 200S SHK 200S 6 Diagram of electrical connections Chapter 13 Technical data...

Страница 71: ...71 SHK 200S SHK 200S 6 Chapter 13 Technical data...

Страница 72: ...72 SHK 200S SHK 200S 6 Chapter 13 Technical data...

Страница 73: ...73 SHK 200S SHK 200S 6 Chapter 13 Technical data...

Страница 74: ...74 SHK 200S SHK 200S 6 Chapter 13 Technical data...

Страница 75: ...75 SHK 200S SHK 200S 6 Chapter 13 Technical data...

Страница 76: ...76 SHK 200S SHK 200S 6...

Страница 77: ...77 SHK 200S SHK 200S 6...

Страница 78: ...78 SHK 200S SHK 200S 6...

Страница 79: ......

Страница 80: ...METRO THERM A S RUNDINSVEJ 55 DK3200 HELSINGE INFO METROTHERM DK WWW METROTHERM DK 08 242 1909...

Отзывы: