3.2.13
Clearances to Combustible Mantels
An
8”
combustible mantel may be installed at a minimum of 12" above the top of the heat outlet (35
” up from the
floor level of
this Insert). Non-combustible (marble, brick, stone, metal etc.) mantels can be installed at any desired height above the top
convection air opening. Any pre-existing combustible mantel must fall within the approved mantel profile chart.
WARNING: If the existing mantel does not conform to required clearances, either remove and relocate the
combustible mantel at an approved height or add a 20 -gage metal shield underneath the combustible mantel
that extends the full width and depth of the co mbustible mantel. Provide
a 1” active air space between the
metal shield and the bottom surface of the combustible mantel. Use ceramic spacers to create the 1” active
air space. See diagram on next page.
Note: The distance from the Floor Level of this Insert to the Top Air Gap is 23
”.
Figure 3-27 Mantel Clearances
Figure 3-28 Minimum Distance from Floor to 8" Mante
l is 35”
Figure 3-29 Approved Mantel Profiles
R-1 RATING REQUIRED
35” TO
AN
8-inch
MANTEL
Содержание FV44I Gen 3
Страница 16: ...85 03 01060 D FV44i D cor Gen 3 Page 16 Figure 3 13 Figure 3 12...
Страница 30: ...85 03 01060 D FV44i D cor Gen 3 Page 30 Figure 3 30 Mantel Clearance Reduction Method...
Страница 87: ...85 03 01060 D FV44i D cor Gen 3 Page 87 6 7 2 Convection Air Blower System Parts Figure 6 3 Blower System Parts...
Страница 88: ...85 03 01060 D FV44i D cor Gen 3 Page 88 6 7 3 Burner System Parts Figure 6 4 Burners Systems Parts...
Страница 97: ...Thank you for choosing Mendota...
Страница 98: ...Johnson Gas Appliance Company 520 E Avenue NW Cedar Rapids Iowa 52405 Mendota Warranty Registration...