wye-connected winding or between pairs of terminals on a delta-connected
winding. Comparison may also be made with original data measured in the
factory.
Testing a Single-Phase Transformer
SINGLE-WINDING TEST
Figure 2: Single Winding Measurement
F
WARNING
Do not disconnect leads until all indicators are OFF!
PROCEDURE:
1.
Connect line cord to unit and plug into 120 V/230 V socket.
2.
Connect Safety GND cord from Top Panel to Transformer GND.
3.
Set the following conditions:
a.
Set to
TEST
position.