DUAL-WINDING TEST
This procedure describes the testing of both windings (high and low) on a single-
phase transformer at the same time.
Figure 3: Dual-Winding Test
F
WARNING
Do not disconnect leads until all indicators are OFF!
NOTES: It should be carefully noted that the jumper in Figure 3 be connected to
opposite polarities of transformer to reduce transformer core saturation
time.
If the resistance between the 2 windings is greater than factor of 10, you
may get a more accurate reading by testing the windings separately.
PROCEDURE:
1.
Connect line cord to unit and plug into line socket.
2.
Connect Safety GND cord from Top Panel to Transformer GND.