Service
AVTMTO210 Rev 7 Sept 2013
61
CODE Error Description
Possible Cause
420
Relay test K2 off test failed
421
Relay test K3 on and K4on failed
422
Relay test K3 off test failed
423
Relay test K4 off test failed
465
OVER and UNDER failed during winding
resistance test
466
Current calibration failed during winding
resistance test
467
Voltage calibration failed during winding
resistance test
468
Received abort signal
469
System zero cal failed during current
regulation
470
No current setting has been set for current
control.
471
Current is flat or dropping while charging
Current leads not connected
472
Break before make error
Lead removed during testing. >10% current
change during testing.
473
H1+ failed, Vrelay3 failed
474
X3+ failed, K9 failed
475 I-SENSE
failed
476
Auto-range, resistance is too high
477
Auto-range, current failed
478
Auto-range, current standard deviation too
high
479
Auto-range, voltage is too low
Содержание MTO210