64
OMM 1008-1
SET UNIT SPs (11)
Max Wtr Flow Rates
Evap WF = 02400 GPM
Cond WF = 03000 GPM
These settings are used to calibrate customer-supplied flow switches.
SET UNIT SPs (12)
STD/Day Light Time
dd/mmm/yyyy
hh:mm:ss Day of week
SET UNIT SPs (13)
Display Format
Units =
°
°
°
°
F/psi (IP)
Lang = English
SET UNIT SPs (14)
Protocol = Modbus
Id#= 001 Units=IP
Baud Rate = 19200
SET UNIT SPs (15)
EX-Val Std Values
Pos 450% L76.0psi
Enthalpy Sp 85.0°F
Set Compressor Setpoints
NOTE: In the following SET COMP screens, the #N field indicates which compressor (#1 or #2 ) is being
set. There is basically a column of menu screens for each compressor.
SET COMP#N SPs (1)
Demand Limit = OFF
Minimum Amps = 010%
Maximum Amps = 100%
Demand Limit settings can be OFF or ON as determined from the Demand Limit setpoint.
SET COMP#N SPs (2)
StageMode = NORMAL
StageSequence# =01
Max Comprs ON =02