62
OMM 1008-1
View Alarms
ALARM LOG 01
Description
hh:mm:ss dd/mmm/yyyy
ALARM LOG 02 to 25
Description
hh:mm:ss dd/mmm/yyyy
ACTIVE ALARM
Time Date
Fault Description
Set Unit Setpoints
The following screens are only shown in
°
F/psi. Setpoint default vales and available setting range can be
found in Table 6 on page 19.
SET UNIT SPs (1)
Unit Enable = OFF
Unit Mode = COOL
Source = SWITCHES
Unit Enable settings can be OFF and ON as determined from the Unit Enable setpoint.
Unit Mode settings can be COOL or TEST as determined from the Unit Mode setpoint (TEST mode is not be
selectable from the 4x20 display/keypad although it may be displayed if already set).
Source settings can be KEYPAD, SWITCHES, or NETWORK as determined from the Mode Source setpoint.
SET UNIT SPs (2)
Available Modes
= COOL
Select w/Unit Off
Available Modes settings for Magnitude chillers can be COOL. The unit must be turned off to change this
setpoint.
SET UNIT SPs (3)
Cool LWT = XX.X
°
°
°
°
F
Ice LWT = XX.XF
Heat LWT = XX.XF
Ignore any setting other than COOL LWT should they appear on this menu.
SET UNIT SPs (4)
Leaving Water Temp
StartDelta= 03.0
°
°
°
°
F
StopDelta = 03.0
°
°
°
°
F