OMM 1008-1
55
Unit Controller Menu Screens
The unit controller, located in the control panel adjacent to the OITS, is the only controller used by the unit
operator. In addition to unit functions, most compressor parameters are viewable on it, and all setpoints can
be accessed from it.
Unit of Measure
SI units of measure can be selected with the appropriate setpoint screen but will appear only on the OITS.
The controller LCD screens read only in inch-pounds unit of measure.
Menu Structure (Hierarchical)
A hierarchical menu structure is used to access the various screens. Each menu screen can have one to four
lines of information. Optionally, the last menu selection can access one of a set of screens that can be
navigated with the UP/DOWN arrow keys (see the scrolled menu structure below). Menu selection is
initiated by pressing the MENU key, which changes the display from a data screen to a menu screen. Menu
selections are then made using the arrow keys according to labels on the right side of the display (the arrows
are ignored). When the last menu item is selected, the display changes to the selected data screen. An
example follows showing the selection of the “VIEW COMPRESSOR” (n) screen.
Suppose the current screen is:
ALARM LOG
(data)
(data)
(data)
After pressing the MENU button, the top-level menu screen will show:
< ALARM
< VIEW
< SET
<
After pressing the “VIEW” menu button, a menu screen will show:
VIEW < COMPRESSOR
< UNIT
< EVAPORATOR
< CONDENSER
After pressing the “COMPRESSOR” menu button, the selected data screen will show:
VIEW COMP (n)
(screen n data)
(screen n data)
(screen n data)
Where “n” is the number of the last viewed COMPRESSOR screen. The arrow keys will automatically return
to the “scroll” mode at this time. Different compressor screens can then be selected with the UP/DOWN
arrow keys.
The complete menu structure follows. Data screens are shown as [data] when a single screen is at the bottom