42
OMM 1008-1
Cooling Tower Bypass VALVE Settings
Figure 20, Tower Bypass VALVE Setpoint Screen
Table 19, Tower Bypass VALVE Setpoints
(See page 44 for complete explanation.)
Description
No.
Default
Range
Pass-
word
Comments
Slope Gain
15
65
10 to 99
M
Control gain for temperature (or lift) slope
Error Gain
14
55
10 to 99
M
Control gain for temperature (or lift) error
Valve Control Range(Max)
13
45%
0 to 100%
M
Maximum valve position, overrides all other settings
Valve Control Range (Min)
12
35%
0 to 100%
M
Minimum valve position, overrides all other settings
Temp - Maximum Start
Position
11
85
°
F
0 to 100
°
F
M
Condenser EWT at which valve should be open to tower.
Valve position is set to SP8
Maximum Start Position
10
80%
0 to 100%
M
Initial valve position when condenser EWT is at or above
Setpoint # 9
Temp - Minimum Position
9
75
°
F
0 to 100
°
F
M
Condenser EWT at which initial valve position is set to
Setpoint # 6
Minimum Start Position
8
10%
0 to 100%
M
Initial position of valve when condenser EWT is at or
below Setpoint # 7
Stage Down @
7
20%
0 to 100%
M
Valve position below which the fans can stage down
(Tower - Setpoint #2 = Valve Stage Down
VFD speed below which the next fan speed can turn off
(Tower - Setpoint # 2 = valve/VFD
Stage Up @
6
80%
0 to 100%
M
Valve position above which the fans can stage up (Tower
- Setpoint #2 = Valve Stage Down
VFD speed above which the next fan speed can turn on
(Tower - Setpoint # 2 = valve/VFD
Valve Deadband (Lift)
5
4.0 psi
1.0 to 20.0 psi
M
Control deadband, Tower - Setpoint #1=Lift
Valve Deadband (Temp)
4
2.0
°
F
1.0 to 10.0
°
F
M
Control deadband, Tower Setpoint #1=Temp
Valve Target (Lift)
3
30 psi
10 to 130 psi
M
Target for lift pressure (Tower - Setpoint #1= Lift), Works
with Setpoint # 5
Valve Setpoint (Temp)
2
65
°
F
40 to 120
°
F
M
Target for condenser EWT (Tower Setpoint #1= Temp),
Works with Setpoint # 4
Valve Type
1
NC (To
Tower)
NC, NO
M
Normally closed (NC) or normal open (NO)
to tower