48
OMM 1008-1
MODES Setpoints
Figure 24, MODES Setpoint Screen
NOTE
: Gray setpoints are not used with Magnitude chillers.
Table 22, MODES Setpoint Settings
Description
No.
Default
Range
Pass-
word
Comments
Comp # 2 Stage
Sequence
10
1
1,2, … (# of
Compressors)
M
Sets sequence number for # 2 compressor, if 1 it is
always first to start, if 2 is always second (Note 1)
Comp # 2 Stage
Mode
9
Normal
Normal, Efficiency,
Pump, Standby
M
Normal uses standard sequencing
Efficiency starts one compressor on each unit
Pump starts all compressors on one chiller first
Standby uses this compressor only if another fails.
Comp #1 Stage
Sequence
8
1
1,2, … (# of
Compressors)
M
Sets sequence number for # 1 compressor, if 1 it is
always first to start, if 2 is always second (Note 1)
Comp #1 Stage
Mode
7
Normal
Normal, Efficiency,
Pump, Standby
M
Ditto No. 9.
Max. Comp. ON
6
1
1-16
M
Total number of compressors minus standby
BAS Protocol
5
MODBUS
None, Local, BACnet,
LonWorks, MODBUS,
Remote
M
Sets BAS Standard Protocol to be used, or LOCAL
if none.
Cond Pump
4
Pump #1
Only
Pump #1 Only, Pump #2
Only, Auto Lead, #1
Primary, #2 Primary
M
Pump #1 Only, Pump #2 Only, use only these
pumps
AUTO, balance hours between #1 and #2
#1 Primary, #2 Primary, if primary fails, use other
Evap Pump
3
Pump #1
Only
Pump #1 Only, Pump #2
Only, Auto Lead, #1
Primary, #2 Primary
M
Pump #1 Only, Pump #2 Only, use only these
pumps
AUTO, balance hours between #1 and #2
#1 Primary, #2 Primary, if primary fails, use other
Control Source
2
LOCAL
LOCAL, BAS, SWITCH
O
Sets control source
Unit Enable
1
OFF
OFF, AUTO
O
OFF, everything is off. AUTO, Evap pump on,
comp, cond pump and tower on as required to
meet LWT
1.
If both compressors have the same sequence number, they will automatically balance starts and run-hours.
2.
See page 68 for further details on pump operation.