20
OMM 1008-1
Description
Default
Range
Type
PW
Stage Up Time
2 min
1 to 60 min
N
M
Stage Down Time
5 min
1 to 60 min
N
M
Stage Differential (Temp)
3.0
°
F
1.0 to 10.0
°
F
N
M
Stage Differential (Lift)
6.0 psi
1.0 to 20.0 psi
N
M
Stage #1 On (Temp)
70
°
F
40 to 120
°
F
N
M
Stage #2 On (Temp)
75
°
F
40 to 120
°
F
N
M
Stage #3 On (Temp)
80
°
F
40 to 120
°
F
N
M
Stage #4 On (Temp)
85
°
F
40 to 120
°
F
N
M
Stage #1 On (Lift)
35 psi
10 to 130 psi
N
M
Stage #2 On (Lift)
45 psi
10 to 130 psi
N
M
Stage #3 On (Lift)
55 psi
10 to 130 psi
N
M
Stage #4 On (Lift)
65 psi
10 to 130 psi
N
M
Cooling Tower Valve / VFD
Valve/VFD Control
None
None, Valve Setpoint, Valve Stage,
VFD Stage, Valve SP/VFD Stage
N
M
Valve Setpoint (Temp)
65
°
F
40 to 120
°
F
N
M
Valve Setpoint (Lift)
30 psi
10 to 130 psi
N
M
Valve Deadband (Temp)
2.0
°
F
1.0 to 10.0
°
F
N
M
Valve Deadband (Lift)
4.0 psi
1.0 to 20.0 psi
N
M
Stage Down @
20%
0 to 100%
N
M
Stage Up @
80%
0 to 100%
N
M
Valve Control Range (Min)
10%
0 to 100%
N
M
Valve Control Range(Max)
90%
0 to 100%
N
M
Valve Type
NC
(To Tower)
NC, NO
N
M
Minimum Start Position
0%
0 to 100%
N
M
Minimum Position @
60
°
F
0 to 100
°
F
N
M
Maximum Start Position
100%
0 to 100%
N
M
Maximum Position @
90
°
F
0 to 100
°
F
N
M
Error Gain
25
10 to 99
N
M
Slope Gain
25
10 to 99
N
M
Alarms
Evaporator Freeze
34.0
°
F
-9.0 to 45.0
°
F
D
T
Condenser Freeze
34.0
°
F
-9.0 to 45.0
°
F
D
T
Low Evap Pressure
26 psi
10 to 45 psi
D
T
Low Evap Pressure-Inhibit
38 psi
20 to 45 psi
D
T
Low Evap Pressure-Unload
31 psi
20 to 45 psi
D
T
High Discharge Temperature-
Shutdown
190
°
F
120 to 240
°
F
N
T
High Discharge Temperature-
Load
170
°
F
120 to 240
°
F
N
T
High Condenser Pressure
140 psi
120 to 240 psi
D
T
Motor Current Threshold
10%
1 to 20%
N
T
Surge High Suction SH - Start
50
°
F
25 to 90
°
F
N
T
Surge High Suction SH - Run
25
°
F
5 to 45
°
F
N
T
Service
Vane Mode
AUTO
AUTO, MANUAL
N
T
Unload Timer
10 sec
10 to 240 sec
N
T
STOP Timer
1 sec
1 to 240 sec
N
T
These setpoints are normally viewed or changed on the OITS.