92
AGZ 035A through 065A
IOMM AGZ-3
3. The charge can be added at any load condition between 25-100% load per circuit but at least two F
fans should be operating per refrigerant circuit if possible. The suction superheat should be in the
6
°
F-12
°
F (3.3
°
C-6.6
°
C) range.
4. Add sufficient charge to clear the liquid line sightglass and until all flashing stops in the sightglass.
Add an extra 15-20 lbs. of reserve to fill the subcooler if the compressor is operating at 50-100%
load.
5. Check the unit subcooling value by reading the liquid line pressure and temperature at the liquid
line near the filter-drier. The subcooling values should be between 6
°
F-20
°
F (6.6
°
C-11.1
°
C). The
subcooling values will be highest at 75-100% load, approximately 12
°
F-20
°
F (6.6
°
C-11.1
°
C) and
lowest at 50% load, approximately 6
°
F-12
°
F (3.3
°
C-6.6
°
C).
6. With outdoor temperatures above 60
°
F (15.6
°
C) all condenser fans should be operating and the
liquid line temperature should be within 5
°
F-10
°
F (2.8
°
C-5.6
°
C) of the outdoor air temperature. At
25-50% load the liquid line temperature should be within 5
°
F (2.8
°
C) of outdoor air temperature
with all fans on. At 75-100% load the liquid line temperature should be within 10
°
F (5.6
°
C) of
outdoor air temperature with all fans on.
7. Overcharging of refrigerant will raise the compressor discharge pressure due to filling of the
condenser tubes with excess refrigerant.
Содержание AGZ 035A
Страница 6: ...6 AGZ 035A through 065A IOMM AGZ 3 Figure 3 Clearance Requirements...
Страница 18: ...18 AGZ 035A through 065A IOMM AGZ 3 Electrical Legend Figure 8 Electrical Legend...
Страница 19: ...IOMM AGZ 3 AGZ 035A through 065A 19 Figure 9 Typical Field Wiring with Global UNT Controller...
Страница 20: ...20 AGZ 035A through 065A IOMM AGZ 3 Figure 10 Typical Field Wiring Diagram with MicroTech Controller...
Страница 21: ...IOMM AGZ 3 AGZ 035A through 065A 21 Figure 11 Single point Connection with FanTrol...
Страница 22: ...22 AGZ 035A through 065A IOMM AGZ 3 Figure 12 Single point Connection with SpeedTrol...
Страница 23: ...IOMM AGZ 3 AGZ 035A through 065A 23 Figure 13 Unit Control Schematic UNT...
Страница 24: ...24 AGZ 035A through 065A IOMM AGZ 3 Figure 14 Staging Schematic UNT...
Страница 25: ...IOMM AGZ 3 AGZ 035A through 065A 25 Figure 15 MicroTech Controller Schematic...
Страница 26: ...26 AGZ 035A through 065A IOMM AGZ 3 Figure 16 Unit Control Schematic MicroTech...
Страница 27: ...IOMM AGZ 3 AGZ 035A through 065A 27 Figure 17 Staging Schematic MicroTech...
Страница 94: ...94 AGZ 035A through 065A IOMM AGZ 3 Notes...
Страница 95: ......