IOMM AGZ-3
AGZ 035A through 065A
61
Circuit Alarm Conditions
The “Circuit Alarm Conditions” are those alarms that only affect one circuit and can stop the
compressors of that circuit. These alarms are:
•
Compressor Motor Protection
•
High Condenser Pressure
•
Mechanical High Pressure Switch
•
Low Evaporator Pressure
•
Refrigerant Freeze Protection
•
Bad Pressure Transducer
The chiller must have the manual reset system alarm conditions cleared before normal operation can
resume. If the alarm that occurred is an auto-clearing alarm, once the condition has corrected, the
chiller will resume normal operation provided the anti-cycle timers have cleared and sufficient load
exists.
System Alarm Conditions
The “System Alarm Conditions” are those alarms that are common to both refrigeration circuits and
require all compressors to be temporarily shut off or locked out, whichever applies. The following
alarm conditions are checked continuously during all modes of operation by the controller. If one of
the following alarm conditions is detected, the mode of the controller will switch to “ Off:Alarm “.
The controller disables all compressor operation by turning off all Compressor Enable Outputs.
Alarm Output #0 would be turned on to notify the operator of the alarm condition. The red “Alarm
Status” light on the front of the control panel will be solid on the alarm condition and the MicroTech
display will show the current alarm condition. System alarm conditions are:
•
Loss of Water Flow
•
Bad Phase /Voltage
•
Chilled Water Freeze Protection
•
Volts Ratio Protection
•
Bad Leaving Water Sensor
The chiller must have the manual reset system alarm conditions cleared before normal operation can
resume. If the alarm that occurred is an auto-clearing alarm, once the condition has corrected, the
chiller will resume normal operation provided the anti-cycle timers have cleared and sufficient load
exists.
Sequence of Operation
Off Conditions
With power supplied to the unit, 115Vac power is applied through the control fuse F1 to the
compressor crankcase heaters (HTR1-4), the compressors motor protectors (MP1-4), the evaporator
heater and the primary of the 24V control circuit transformer. The 24V transformer provides power
to the MicroTech controller and related components. With 24V power applied, the controller will
check the position of the front panel System Switch. If the switch is in the “stop” position the chiller
will remain off and the display will indicate the operating mode to be OFF:System Sw. The controller
will then check the PumpDown Switches. If either switch is n the “stop” position, that circuit’s
operating mode will be displayed as OFF:PumpDownSw. If the remote Start/Stop Switch is open, the
chiller will be OFF:Remote Sw. The chiller can also be commanded off via the communications
network if a separate System Master Panel is installed. The display will show OFF:Remote Comm if
this operating mode is in effect.
Содержание AGZ 035A
Страница 6: ...6 AGZ 035A through 065A IOMM AGZ 3 Figure 3 Clearance Requirements...
Страница 18: ...18 AGZ 035A through 065A IOMM AGZ 3 Electrical Legend Figure 8 Electrical Legend...
Страница 19: ...IOMM AGZ 3 AGZ 035A through 065A 19 Figure 9 Typical Field Wiring with Global UNT Controller...
Страница 20: ...20 AGZ 035A through 065A IOMM AGZ 3 Figure 10 Typical Field Wiring Diagram with MicroTech Controller...
Страница 21: ...IOMM AGZ 3 AGZ 035A through 065A 21 Figure 11 Single point Connection with FanTrol...
Страница 22: ...22 AGZ 035A through 065A IOMM AGZ 3 Figure 12 Single point Connection with SpeedTrol...
Страница 23: ...IOMM AGZ 3 AGZ 035A through 065A 23 Figure 13 Unit Control Schematic UNT...
Страница 24: ...24 AGZ 035A through 065A IOMM AGZ 3 Figure 14 Staging Schematic UNT...
Страница 25: ...IOMM AGZ 3 AGZ 035A through 065A 25 Figure 15 MicroTech Controller Schematic...
Страница 26: ...26 AGZ 035A through 065A IOMM AGZ 3 Figure 16 Unit Control Schematic MicroTech...
Страница 27: ...IOMM AGZ 3 AGZ 035A through 065A 27 Figure 17 Staging Schematic MicroTech...
Страница 94: ...94 AGZ 035A through 065A IOMM AGZ 3 Notes...
Страница 95: ......