56
AGZ 035A through 065A
IOMM AGZ-3
Controller Inputs /Outputs
Analog Inputs
Analog inputs are used to read the various temperatures and pressures on the chiller as well as any
customer supplied 4-20ma reset signals. The controller’s internal regulated 5Vdc and 12Vdc supplies
provide correct operating voltage for the sensors. See Table 17 for details.
Table 17, Analog Inputs
Input
LED
Description
Location
Range
Resolution
0
0
Leaving Chilled Water Temp
Leaving Chw nozzle
-40 to 263°F
0.1°F
1
1
Circuit #1 Evap Pressure
Circuit #1 Suction Line
0 to 145 psi
0.1 psi
2
2
Circuit #2 Evap Pressure
Circuit #2 Suction Line
0 to 145 psi
0.1 psi
3
3
Circuit #1 Cond Pressure
Compressor Discharge Line-
20 to 450 psi
0.5 psi
4
4
Circuit #2 Cond Pressure
Compressor Discharge Line-
20 to 450 psi
0.5 psi
5
5
Voltage Ratio Signal
EnGinn Power Supply
4.1 to 5.1 VDC
--
6
6
Chw Water Reset
Supplied by others
4 to 20 ma DC
--
7
7
Demand Limit Signal
Supplied by others
4 to 20 ma DC
--
8
8
Entering Evap Water Temp
Entering Chw Nozzle
-40 to 263°F
0.1°F
9
9
Entering Cond Water Temp
Enter Cond Water Nozzle
-40 to 263°F
0.1°F
10
10
Leaving Cond Water Temp
Leaving Cond Water Nozzle
-40 to 263°F
0.1°F
11
11
% Total Unit Amps
Control Cabinet
0 to 4 VDC
--
12
12
Circuit #1 Suction Temp
Circuit #1 Suction Line
-40 to 263°F
0.1°F
13
13
Circuit #2 Suction Temp
Circuit #2 Suction Line
-40 to 263°F
0.1°F
14
14
Circuit #1 Liquid Line Temp
Circuit #1 Liquid Line
-40 to 263°F
0.1°F
15
15
Circuit #2 Liquid Line Temp
Circuit #2 Liquid Line
-40 to 263°F
0.1°F
Digital Inputs
All Digital Inputs are 24Vac. At 7.5Vac to 24Vac the digital input contacts are considered closed.
Below 7.5Vac, the contracts are considered open. See Table 18 for details and operating
characteristics.
Table 18, Digital Inputs
Input
LED
Description
Circuit
Closed
Open
0
0
Mechanical High Pressure Switch
Circuit #1
Normal
Alarm
1
1
2
2
Motor Protect Switch Compressor
Compressor #1
Normal
Alarm
3
3
4
4
Motor Protect Switch Compressor
Compressor #3
Normal
Alarm
5
5
System Switch
Unit
Run
Stop
6
6
Phase/Voltage Monitor
Unit
Normal
Alarm
7
7
Pumpdown Switch
Unit
Pmp Dn
Normal
8
8
Mechanical High Pressure Switch
Circuit #2
Normal
Alarm
9
9
10
10
Motor Protection Switch
Compressor #2
Normal
Alarm
11
11
12
12
Motor Protection Switch
Compressor #4
Normal
Alarm
13
13
Chiller Remote Stop Switch
Unit
Run
Stop
14
14
Evap Water Flow Switch
Unit
Run
Stop
15
15
Pumpdown Switch
Circuit #2
Pmp Dn
Normal
Содержание AGZ 035A
Страница 6: ...6 AGZ 035A through 065A IOMM AGZ 3 Figure 3 Clearance Requirements...
Страница 18: ...18 AGZ 035A through 065A IOMM AGZ 3 Electrical Legend Figure 8 Electrical Legend...
Страница 19: ...IOMM AGZ 3 AGZ 035A through 065A 19 Figure 9 Typical Field Wiring with Global UNT Controller...
Страница 20: ...20 AGZ 035A through 065A IOMM AGZ 3 Figure 10 Typical Field Wiring Diagram with MicroTech Controller...
Страница 21: ...IOMM AGZ 3 AGZ 035A through 065A 21 Figure 11 Single point Connection with FanTrol...
Страница 22: ...22 AGZ 035A through 065A IOMM AGZ 3 Figure 12 Single point Connection with SpeedTrol...
Страница 23: ...IOMM AGZ 3 AGZ 035A through 065A 23 Figure 13 Unit Control Schematic UNT...
Страница 24: ...24 AGZ 035A through 065A IOMM AGZ 3 Figure 14 Staging Schematic UNT...
Страница 25: ...IOMM AGZ 3 AGZ 035A through 065A 25 Figure 15 MicroTech Controller Schematic...
Страница 26: ...26 AGZ 035A through 065A IOMM AGZ 3 Figure 16 Unit Control Schematic MicroTech...
Страница 27: ...IOMM AGZ 3 AGZ 035A through 065A 27 Figure 17 Staging Schematic MicroTech...
Страница 94: ...94 AGZ 035A through 065A IOMM AGZ 3 Notes...
Страница 95: ......