76
AGZ 035A through 065A
IOMM AGZ-3
Table 42, MENU 20 Schedule
Screen
Display
Factory Setpoint
Range
1
Override= xx.xx hr
0.00 Hr
00:00 - 63.50
2
NMPSchedule= N/A
N/A
3
Sun 00:00-23:59
00:00 - 23:59
00:00 - 23:59
4
Mon 00:00-23:59
00:00 - 23:59
00:00 - 23:59
5
Tue 00:00-23:59
00:00 - 23:59
00:00 - 23:59
6
Wed 00:00-23:59
00:00 - 23:59
00:00 - 23:59
7
Thu 00:00-23:59
00:00 - 23:59
00:00 - 23:59
8
Fri 00:00-23:59
00:00 - 23:59
00:00 - 23:59
9
Sat 00:00-23:59
00:00 - 23:59
00:00 - 23:59
10
Hol 00:00-23:59
00:00 - 23:59
00:00 - 23:59
Table 43, MENU 21 Holiday Date
Screen
Display
Factory Setpoint
Range
1
#1 Date = N/A 0
N/A 0
Jan - Dec 1 - 31
2
#1 Dur = 0 Day(s)
0
0 - 31
3
#2 Date = N/A 0
N/A 0
Jan - Dec 1 - 31
4
#2 Dur = 0 Day(s)
0
0 - 31
5
#3 Date = N/A 0
N/A 0
Jan - Dec 1 - 31
6
#3 Dur = 0 Day(s)
0
0 - 31
7
#4 Date = N/A 0
N/A 0
Jan - Dec 1 - 31
8
#4 Dur = 0 Day(s)
0
0 - 31
9
#5 Date = N/A 0
N/A 0
Jan - Dec 1 - 31
10
#5 Dur = 0 Day(s)
0
0 - 31
11
#6 Date = N/A 0
N/A 0
Jan - Dec 1 - 31
12
#6 Dur = 0 Day(s)
0
0 - 31
13
#7 Date = N/A 0
N/A 0
Jan - Dec 1 - 31
14
#7 Dur = 0 Day(s)
0
0 - 31
15
#8 Date = N/A 0
N/A 0
Jan - Dec 1 - 31
16
#8 Dur = 0 Day(s)
0
0 - 31
17
#9 Date = N/A 0
N/A 0
Jan - Dec 1 - 31
18
#9 Dur = 0 Day(s)
0
0 - 31
19
#10 Date = N/A 0
N/A 0
Jan - Dec 1 - 31
20
#10 Dur = 0 Day(s)
0
0 - 31
21
#11 Date = N/A 0
N/A 0
Jan - Dec 1 - 31
22
#11 Dur = 0 Day(s)
0
0 - 31
23
#12 Date = N/A 0
N/A 0
Jan - Dec 1 - 31
24
#12 Dur = 0 Day(s)
0
0 - 31
25
#13 Date = N/A 0
N/A 0
Jan - Dec 1 - 31
26
#13 Dur = 0 Day(s)
0
0 - 31
27
#14 Date = N/A 0
N/A 0
Jan - Dec 1 - 31
28
#14 Dur = 0 Day(s)
0
0 - 31
Table 44, MENU 22 Alarm Spts
Values for R-22 refrigerant, ( ) indicates Centigrade values
Screen
Display
Factory Setpoint
Range
1
FreezStat= xxpsi (kPa)
54 (372)
20 - 60 (138 - 414)
2
FreezH2O= xx.x °F (°C)
36.0 (2.3)
0.0 - 40.0 (-17.5 - 4.5)
3
FreezeTim= xxx sec
4
Hi Press = xxxpsi (kPa)
380 (2622)
280 - 426 (1932 - 2939)
Table 45, MENU 22 Alarm Spts
Values for 134a refrigerant, ( ) indicates Centigrade values
Screen
Display
Factory Setpoint
Range
1
FreezStat= xxpsi (kPa)
26 (179)
4 - 26 (27 - 179)
2
FreezH2O= xx.x °F (°C)
36.0 (2.3)
0.0 - 40.0 (-17.5 - 4.5)
3
FreezeTim= xxx sec
4
Hi Press = xxxpsi (kPa)
380 (2622)
280 - 426 (1932 - 2939)
Содержание AGZ 035A
Страница 6: ...6 AGZ 035A through 065A IOMM AGZ 3 Figure 3 Clearance Requirements...
Страница 18: ...18 AGZ 035A through 065A IOMM AGZ 3 Electrical Legend Figure 8 Electrical Legend...
Страница 19: ...IOMM AGZ 3 AGZ 035A through 065A 19 Figure 9 Typical Field Wiring with Global UNT Controller...
Страница 20: ...20 AGZ 035A through 065A IOMM AGZ 3 Figure 10 Typical Field Wiring Diagram with MicroTech Controller...
Страница 21: ...IOMM AGZ 3 AGZ 035A through 065A 21 Figure 11 Single point Connection with FanTrol...
Страница 22: ...22 AGZ 035A through 065A IOMM AGZ 3 Figure 12 Single point Connection with SpeedTrol...
Страница 23: ...IOMM AGZ 3 AGZ 035A through 065A 23 Figure 13 Unit Control Schematic UNT...
Страница 24: ...24 AGZ 035A through 065A IOMM AGZ 3 Figure 14 Staging Schematic UNT...
Страница 25: ...IOMM AGZ 3 AGZ 035A through 065A 25 Figure 15 MicroTech Controller Schematic...
Страница 26: ...26 AGZ 035A through 065A IOMM AGZ 3 Figure 16 Unit Control Schematic MicroTech...
Страница 27: ...IOMM AGZ 3 AGZ 035A through 065A 27 Figure 17 Staging Schematic MicroTech...
Страница 94: ...94 AGZ 035A through 065A IOMM AGZ 3 Notes...
Страница 95: ......