IOMM AGZ-3
AGZ 035A through 065A
17
Table 11, AGZ035A - 065A, 60 Hz Single Point Power, Field Wiring Data (continued)
Wiring to Standard
Power Block
Wiring to Optional
Non-Fused Disconnect Switch
AGZ
Unit
Size
Volts
Terminal
Amps
Connector Wire Range
(Copper Wire Only)
Terminal
Amps
Connector Wire Range
(Copper Wire Only)
208
335
# 4 - 400 MCM
225
#4 – 4/0
230
335
# 4 - 400 MCM
225
#4 – 4/0
380
335
# 4 - 400 MCM
150
#4 – 4/0
460
175
#12 - 2/0
150
#4 - 4/0
050E
575
175
#12 - 2/0
150
#4 - 4/0
208
335
# 4 - 400 MCM
400
250 - 500 MCM
230
335
# 4 - 400 MCM
400
250 - 500 MCM
380
335
# 4 - 400 MCM
250
#4 - 350 MCM
460
175
#12 - 2/0
150
#4 - 4/0
055A
575
175
#12 - 2/0
150
#4 - 4/0
208
335
# 4 - 400 MCM
400
250 - 500 MCM
230
335
# 4 - 400 MCM
400
250 - 500 MCM
380
335
# 4 - 400 MCM
250
#4 - 350 MCM
460
175
#12 - 2/0
150
#4 - 4/0
060A
575
175
#12 - 2/0
150
#4 - 4/0
208
335
# 4 - 400 MCM
400
250 - 500 MCM
230
335
# 4 - 400 MCM
400
250 - 500 MCM
380
335
# 4 - 400 MCM
250
#4 - 350 MCM
460
175
#12 - 2/0
150
#4 - 4/0
065A
575
175
#12 - 2/0
150
#4 - 4/0
Notes for “Electrical Data Single Point” Power:
1.
Unit wire size ampacity (MCA) is equal to 125% of the largest compressor-motor RLA plus 100% of RLA
of all other loads in the circuit including the control transformer.
2.
If the control transformer option is furnished, no separate 115V power is required.
3.
If a separate 115V power supply is used for the control circuit, then the wire sizing amps is 10 amps for all
unit sizes.
4.
Recommended power lead wire sizes for 3 conductors per conduit are based on 100% conductor ampacity
in accordance with NEC. Voltage drop has not been included. Therefore, it is recommended that power
leads be kept short. All terminal block connections must be made with copper (type THW) wire.
5.
“Recommended Fuse Sizes” are selected at approximately 150% to 175% of the largest compressor RLA,
plus 100% of all other loads in the circuit.
6.
“Maximum Fuse Sizes” are selected at approximately 225% of the largest compressor RLA, plus 100% of
all other loads in the circuit.
7.
The recommended power lead wire sizes are based on an ambient temperature of 86°F. Ampacity
correction factors must be applied for other ambient temperatures. Refer to the National Electrical Code
Handbook.
8.
The MCA may vary slightly depending on fan motor options such as SpeedTrol, TEFC.
Power Limitations:
Volts within
±
10 percent of nameplate rating. Phase unbalance maximum of 3 percent.
Notes for “Compressor and Condenser Fan Amp Draw”:
1.
Compressor RLA values are for wiring sizing purposes only but do not reflect normal operating current
draw at rated capacity. If unit is equipped with SpeedTrol condenser fan motors, the first motor on each
refrigerant circuit is a single phase, 1hp motor, with a FLA of 2.8 amps at 460 volts, 5.6 amps at 208, 230,
380, and 575 volts.
2.
Compressor LRA for reduced inrush start are for the first winding only. If the unit is equipped with
SpeedTrol motors, the first motor is a single phase, 1 hp motor, with a LRA of 7.3 amps at 460 volts, 14.5
amps at 208, 230, 380, and 575 volts.
Notes for “Field Wiring Data”
1.
Requires a single disconnect to supply electrical power to the unit. This power must be fused.
2.
All field wiring to unit power block or optional non-fused disconnect switch must be copper.
3.
All field wire size values given in table apply to 75°C rated wire per NEC.
Содержание AGZ 035A
Страница 6: ...6 AGZ 035A through 065A IOMM AGZ 3 Figure 3 Clearance Requirements...
Страница 18: ...18 AGZ 035A through 065A IOMM AGZ 3 Electrical Legend Figure 8 Electrical Legend...
Страница 19: ...IOMM AGZ 3 AGZ 035A through 065A 19 Figure 9 Typical Field Wiring with Global UNT Controller...
Страница 20: ...20 AGZ 035A through 065A IOMM AGZ 3 Figure 10 Typical Field Wiring Diagram with MicroTech Controller...
Страница 21: ...IOMM AGZ 3 AGZ 035A through 065A 21 Figure 11 Single point Connection with FanTrol...
Страница 22: ...22 AGZ 035A through 065A IOMM AGZ 3 Figure 12 Single point Connection with SpeedTrol...
Страница 23: ...IOMM AGZ 3 AGZ 035A through 065A 23 Figure 13 Unit Control Schematic UNT...
Страница 24: ...24 AGZ 035A through 065A IOMM AGZ 3 Figure 14 Staging Schematic UNT...
Страница 25: ...IOMM AGZ 3 AGZ 035A through 065A 25 Figure 15 MicroTech Controller Schematic...
Страница 26: ...26 AGZ 035A through 065A IOMM AGZ 3 Figure 16 Unit Control Schematic MicroTech...
Страница 27: ...IOMM AGZ 3 AGZ 035A through 065A 27 Figure 17 Staging Schematic MicroTech...
Страница 94: ...94 AGZ 035A through 065A IOMM AGZ 3 Notes...
Страница 95: ......