Checking the Air Supply
Use this procedure to check the air supply.
1. Turn on the air supply.
2. Adjust the filter regulator.
3. Supply pressure must be a minimum of 10 psi greater than the spring range of the
actuator but can not exceed the rated actuator pressure. Refer to the valve or actuator
instruction manual.
4. Inspect the tubing connections between the filter-regulator and the PST controller for
leaks.
5. Verify that the tubing is not bent or crushed.
6. Verify that all fittings are leak tight.
NOTE
Do not use Teflon pipe seal tape. The Teflon tape can shred into
particles that are harmful to the pneumatic components.
For detailed information on pneumatic connections refer to “Pneumatic Connections” on
page 73.
Wiring the SVI II ESD
There are two components to wiring the SVI II ESD; making an electrical connection for power
and making a local control loop connection for HART
®
communication.
Electrical Connection Guidelines
When making the SVI II ESD electrical connections, follow these guidelines:
1. The SVI II ESD device is available in two control signal configurations: 4-20 mA or
0/24 VDC.
2. Provide sufficient electrical isolation between adjacent signal lines and between signal
lines and ground for all wiring.
3. Use stranded 14 to 22 AWG (or equivalent gauge and flexibility).
4. Use conduit sealant to prevent condensation from entering the enclosure and, in Class 1
Div. 2 conditions to prevent hazardous gases and vapors from migrating through the
conduit to the control room or an open ignition source.
5. Wire according to the National Electrical Code (ANSI-NFPA 70) or other applicable local
codes.
6. The terminal clamps are designed for one wire only; DO NOT attempt to terminate
multiple wires into one terminal.
Содержание SVI II ESD
Страница 4: ...This page intentionally left blank ...
Страница 10: ...This page intentionally left blank ...
Страница 14: ...This page intentionally left blank ...
Страница 100: ...This page intentionally left blank ...
Страница 120: ...This page intentionally left blank ...
Страница 126: ...This page intentionally left blank ...
Страница 160: ...This page intentionally left blank ...
Страница 194: ...This page intentionally left blank ...
Страница 200: ...This page intentionally left blank ...
Страница 204: ...This page intentionally left blank ...
Страница 206: ...This page intentionally left blank ...
Страница 208: ...This page intentionally left blank ...
Страница 216: ...This page intentionally left blank ...