RAM_
CHECKSUM
2
No
Yes/No
Yes/Yes
RAM
Check-
sum
Error
1- A corruption of
the content in vol-
atile memory
occurred.
1- Notify factory
at svisup-
[email protected].
27
3
2
FW_
CHECKSUM
1
No
No/No
Yes/Yes
Flash
Check-
sum
Error
1- Invalid firm-
ware checksum
due to data cor-
ruption.
1- Remove power
to the device for 2
minutes and
restart it.
2- If the failure
persists, Replace
device.
28
3
3
STACK
2
No
Yes/No
Yes/Yes
Stack
Error
1- A problem with
the memory stack
occurred.
1- Clear the condi-
tion using ValVue
ESD or HART
®
Host.
29
3
4
FACTORYMODE 1
No
Yes/No
Yes/No
Factory
Mode
Fault
1- Device is in the
factory mode.
1- Replace device
and report the
problem at svi-
sup-
[email protected].
30
3
5
NVM_TEST
2
No
Yes/No
Yes/Yes
NVM Test
Error
1- A problem
occurred when
testing non-vola-
tile memory.
1- 1- Clear the
condition using
ValVue ESD or
HART
®
Host.
31
3
6
LATCH_FSAFE
1
NA
Yes/Yes
No/Yes
Reserved
(3-6)
NA
NA
32
3
7
Undefined
(reserved)
3
NA
NA/NA
Yes/No
Reserved
(3-7)
NA
NA
33
4
0
REF_
VOLTAGE
1
No
Yes/No
Yes/No
Ref Volt-
age Fault
1- A component
problem is affect-
ing the circuit
board's reference
voltage.
1- Replace the
device and report
problem at svi-
sup-
[email protected].
34
4
1
POSITION_
SENSOR
1
No
Yes/No
Yes/No
Position
Sensor
Fault
1- Electronic hall
sensor compo-
nent and related
components
failed.
1- Replace device
and report prob-
lem at svisup-
[email protected].
35
4
2
CURRENT_
SENSOR
1
No
Yes/No
Yes/No
Current
Sensor
Fault
1- Electronic input
loop current sen-
sor is damaged.
1- Replace device
and report prob-
lem at svisup-
[email protected].
36
4
3
TEMPERATURE_
SENSOR
1
No
Yes/No
Yes/Yes
Tem-
perature
Sensor
Fault
1- Electronic tem-
perature sensor is
damaged.
1- Replace device
and report prob-
lem at svisup-
[email protected].
Table 13 SVI II ESD Fault Matrix (Continued)
Sequence
Byte
#
Bit
#
FAULT Name
Criticality
of Alarm
Auto-
mati-
cally
cleared
Can be
cleared/
Persists
across
resets
Non-
Mas-
kable/
Annunci-
ated
TEXT For
DD &
ValVue
ESD2
English
Probable Cause
English
Recommended
Action
Содержание SVI II ESD
Страница 4: ...This page intentionally left blank ...
Страница 10: ...This page intentionally left blank ...
Страница 14: ...This page intentionally left blank ...
Страница 100: ...This page intentionally left blank ...
Страница 120: ...This page intentionally left blank ...
Страница 126: ...This page intentionally left blank ...
Страница 160: ...This page intentionally left blank ...
Страница 194: ...This page intentionally left blank ...
Страница 200: ...This page intentionally left blank ...
Страница 204: ...This page intentionally left blank ...
Страница 206: ...This page intentionally left blank ...
Страница 208: ...This page intentionally left blank ...
Страница 216: ...This page intentionally left blank ...