ELECTRIC SYSTEM
18000 SERIVCE/MAINTENANCE MANUAL
3-14
Published 12-05-17, Control # 035-23
NODE 5 - Alarms, Pump Controls, and Limits
Reference Electrical Schematic A06374 - Sheets 9, 19, 20 and 21
.
44-a
Ground
Left Rear Jack Retract Solenoid
Ground
44-b
DO-22
Left Rear Jack Retract Solenoid
0 Volts Off; 24 Volts On
CAN35-3-32
44-g
Ground
Jumper to Node Select 3
Ground
44-k
NS-3
Node Select 3 Jumper to Ground
0 Volts (With Jumper)
J6
Receptacle – Mast
46-A
Ground
Drum 3 Diverter Solenoid
Ground
46-B
DO-7
Drum 3 Diverter Solenoid
0 Volts Off; 24 Volts On
CAN35-1-64
46-C
Ground
Drum 5 Diverter Solenoid
Ground
46-D
DO-8
Drum 5 Diverter Solenoid
0 Volts Off; 24 Volts On
CAN35-1-128
46-E
Ground
Mast Raise Solenoid
Ground
46-F
DO-9
Mast Raise Solenoid
0 Volts Off; 24 Volts On
CAN35-2-1
46-G
Ground
Mast Lower Solenoid
Ground
46-H
DO-10
Mast Lower Solenoid
0 Volts Off; 24 Volts On
CAN35-2-2
46-M
NS-3
Node Select 4 Jumper to Ground
0 Volts (With Jumper)
46-U
Ground
Jumper to Node Select 4
Ground
46-V
5 Volts
Mast Angle Sensor
5 Volts
46-W
Ground
Mast Angle Sensor
Ground
46-a
AI-9
Mast Angle Sensor
5 Volts DC Mast at Vertical CAN14-2
1
1
– Lower four bits are the most significant bit of the analog value.
Can ID. No.
Function
Type
Description
Test Voltage
Packet No.
WN16-A/WN14-A
24 Volts
From Node 0 to Node 9
24 Volts Nominal
WN16-C/WN14-C
CANH
Can High Wire Transmission
N/A
WN16-D/WN14-D
Ground
From Node 0 to Node 9
Ground
WN16-F/WN14-F
CANL
Can Low Wire Transmission
N/A
J3
Receptacle – Alarms
53-B
DO-1
Hydraulic Vacuum Switch
0 Volts Off; 24 Volts On
CAN38-1-1
53-C
Ground
Cooler Fan Pump Control (Tier 4)
Ground
53-D
DO-2
Return Line Filter 2 Alarm Switch
0 Volts Off; 24 Volts On
CAN38-1-2
53-E
Ground
Cooler Fan Pump Control (Tier 4)
Ground
53-F
DO-3
Hydraulic Fluid Low Temperature Switch
(Tier 2 and Tier 3)
0 Volts Off; 24 Volts On
CAN38-1-4
53-F
DO-3
Cooler Fan Pump Control - Primary Coil
(Tier 4)
for Values
CAN38-1-4
53-H
DO-4
Return Line Filter 3 Alarm Switch
0 Volts Off; 24 Volts On
CAN38-1-8
53-J
Ground
Jumper to Node Select 4
Ground
53-P
DO-6
Return Line Filter 1 Alarm Switch
0 Volts Off; 24 Volts On
CAN38-1-32
Can ID. No.
Function
Type
Description
Test Voltage
Packet No.
Содержание 18000
Страница 1: ...R e f e r e n c e O n l y Service Maintenance Manual Manitowoc 18000 ...
Страница 2: ...R e f e r e n c e O n l y ...
Страница 4: ...R e f e r e n c e O n l y THE ORIGINAL LANGUAGE OF THIS PUBLICATION IS ENGLISH ...
Страница 210: ...R e f e r e n c e O n l y NOTES SKETCHES AND PHOTOGRAPHS ...
Страница 315: ...R e f e r e n c e O n l y ...
Страница 316: ...R e f e r e n c e O n l y ...