21
© 2016 Sensata Technologies
Setup
3.2 External
Settings
The generator run time, temperature, and voltage settings come
pre-set directly from the factory. For the majority of customers,
the factory default settings as shown in Table 3-2 are appropriate.
If you need to make changes to the factory settings, you can do so
by rotating the knobs on the front panel of the AGS controller either
clockwise or counterclockwise (Figure 3-3).
QUIET TIME
PM/AM
setting
CLOCK
AM/PM
setting
START
VOLTS DC
setting
START
TEMP
°F
setting
RUN TIME
HOURS
setting
RUN TIME HOURS:
This setting determines the length of time
the generator runs once started. The generator starts because the
battery voltage has fallen to the
START VOLTS DC
setting for at least
two continuous minutes; or, the temperature around the remote
switch has risen to the
START TEMP °F
setting. The run time can be
set from 1-5 hours. To change this setting, slowly rotate the knob
marked
RUN TIME HOURS
clockwise to increase generator run time
or counterclockwise to decrease the generator run time.
START TEMP °F:
This setting allows you to enable and adjust a
temperature value that causes the generator to automatically start.
When the temperature around the AGS switch increases to the
START TEMP °F
setting, the generator automatically starts and runs
based on the
RUN TIME HOURS
setting. The AGS attempts to start
Table 3-2, ME-AGS-S Default Settings
Figure 3-3, External Settings
Adjustable Settings
Factory Default Values
RUN TIME HOURS
2 (Hours)
START TEMP °F
OFF (disabled)
START VOLTS DC
11 (Volts DC)
CLOCK AM/PM
8A (8 AM)
QUIET TIME PM/AM
OFF (disabled)
INPUT DC VOLTAGE
12 Volts (bottom two pins)
GEN TYPE
QD Mode (all 4 switches off)
External
Settings
Internal
Settings