© 2016 Sensata Technologies
Installation
2.4
Connecting the Communication Cable
After connecting one end of the communication cable to the back of
the AGS remote switch, connect the other end of the cable to the
REMOTE port (purple label) on the AGS controller (see Figure 2-4).
Info:
The communication cable is a 6-conductor,
fl
at, data
standard with RJ12 (6-position/6-wire) connectors on each end
(see Figure 2-5). The 25’ communications cable may be
extended to a maximum of 250 feet if needed
.
Remote Switch
(backside)
Communications
Cable
Figure 2-4, Communication Cable Connection
Figure 2-5, Communication Cable (Data Type)
123
4
56
123
4
56
white
blue
TAB
TAB
Same colors from
top to bottom
(tabs facing toward you)
2.4.1 Communication
Cable
The 6-conductor communications cable has a RJ12 (6-position/6-
wire) connector on each end and is wired as a
data type
cable. This
means that when the RJ12 connectors are held side by side with
both of the connector tabs facing the same way, the color of the
conductors in each connector is the same from top to bottom (as
shown in Figure 2-5).
2.5
ME-AGS-S Terminal Block Wiring
Refer to Figure 2-7 when wiring the generator to the controller’s
terminal block.
The AGS should already be mounted and the 8-port friction-
fi
t
terminal block unplugged (pull straight out). Ensure the terminal
openings are unscrewed enough to allow wires to be inserted.