
13
© 2016 Sensata Technologies
Installation
Figure 2-7, Wiring to the AGS Controller’s Terminal Block
1
2 3 4 5 6 7 8
RY1
NC
COM
NO
NC
COM
NO
NC
COM
NO
Common (COM) contact on Relay 3 (RY3)
Normally Open (N.O.)
contact on Relay 3 (RY3)
Common (COM) contact on
Relay 1 (RY1) and Relay 2 (RY2)
Normally Open (N.O.)
contact on Relay 2 (RY2)
Normally Open (N.O.)
contact on Relay 1 (RY1)
8
7
6
Relays Inside the AGS controller
Positive DC voltage input [positive terminal from
monitored battery bank (9-64 VDC)]
Negative DC voltage input (negative/ground
terminal from monitored battery bank)
Positive run sense input
(10-40 VDC only when generator is running)
3
4
1
2
RY2
RY3
5
The connection points to each relay are as follows (see Figure 2-7):
2.6
Common ME-AGS-S Generator Wiring Diagrams
The most common generator starting/run/stop circuits can be
divided into three major types: two-wire, three-wire “momentary”,
or three-wire “maintain”. See Figures 2-9 through 2-12 for examples.
Info:
The term “three-wire” refers to the minimum number
of wires required to control the starter motor and to run the
generator—more than three wires may actually be needed.