5
© 2016 Sensata Technologies
Installation
2.0 Installation
Installing the ME-AGS-S is a simple process. Before installing, read
this entire section to familiarize yourself with all aspects of the
installation; then, you can thoroughly plan the details to ensure
the overall system requirements are accomplished. To assist you in
planning and designing your installation, review the basic system
diagram shown in Figure 2-1.
WARNING:
The ME-AGS-S is not an ignition-protection
rated device and should not be installed in any location that
requires ignition-protected equipment. To prevent
fi
re or
explosion, do not install the AGS controller in any area with
extremely
fl
ammable liquids like gasoline or propane; or, in
an area that contains connections between components of
a fuel system.
CAUTION:
Installation should be performed by quali
fi
ed
personnel, such as a licensed or certified electrician.
The installer is responsible for determining which safety
codes apply and for ensuring that applicable installation
requirements are followed. Applicable installation codes vary
depending on the speci
fi
c location and application.
CAUTION:
Review the “Important Product Safety Information”
on pages ii-iii before any installation.
2.1 Installation
Requirements
Review the following requirements before installing this device:
• For the AGS to automatically start and stop the generator
properly, the generator must include an electric start and
an automatic choke. To prevent generator damage and
obtain reliable operation, use generator models designed for
unattended operation. These models should also be equipped
with remote operation connections and have protective systems
that cause the generator to shut down during low oil pressure,
over-temperature, starter lockout, and over-crank conditions.
• T
he ME-AGS-S controller is connected to the remote switch by a
25’ communications cable. Before installing the ME-AGS-S and
connecting any wires, determine: 1) the communications cable
route throughout the home or vehicle/boat from the controller
to the remote switch, 2) the start/stop signal wire route from
the AGS controller to the generator, and 3) the wire route from
the AGS controller to the monitored battery bank.
Info:
Sensata offers two pigtail adapters (ME-PT1 and ME-
PT2) that externally enable the ME-AGS-S to automatically
turn the generator on/off via a manually controlled switch or
an automatically controlled switching device. See Appendix
A for more information.