41-621.1 HART
®
to Modbus
®
Adaptor Operating Manual
49
14.4.21
Right-click on the Comm DTM Project item and select Additional functions\Change dtm
address. Click on the Change address button. Select the address number corresponding
to the attached Model 706 device, then click Close.
14.4.22
Right-click on the Comm DTM Project item and select Connect.
14.4.23
Right-click on the Comm DTM Project item and select Additional functions\Change device
address. The DTM will scan for attached devices and display them in a list. If necessary,
click on the Refresh button.
14.4.24
Ensure that the attached Model 706 is listed and is shown with the correct Poll Address.
14.4.25
Right-click on the Comm DTM Project item and select Connect.
14.4.26
Double click on the device entry in the Project tree to open the Online parameterization
window.
14.4.27
Ensure that the DTM communicates with the device and features such are changing
parameters and viewing Echo Curves, Echo History (as appropriate) and Trend Data are
operational.
14.4.28
Close the Online parameterization window.
14.4.29
Right-click on the Comm DTM Project item and select Disconnect.
14.4.30
Right-click on the Comm DTM Project item and select Parameter. Set both the Start
address and End address to 63, then click OK.
14.4.31
Right-click on the Comm DTM Project item and select Connect.
14.4.32
Right-click on the Comm DTM Project item and select Additional functions\Scan list. The
DTM will scan for attached device, sending a HART Command 0 with an address of 63.
Receipt of that command by the HMA will cause it to reboot into the Normal operating
mode.
14.4.33
Shut down PACTware.
14.4.34
Open the Terminal application.
14.4.35
Click on the Connect button.
14.4.36
Create a Transmit Macro that will send Uxx?$0D to an attached device and check the
checkbox to the right of the macro definition. Note that the xx in the macro represents
the Poll Address of the target device.