41-621.1 HART
®
to Modbus
®
Adaptor Operating Manual
18.4.8
For the Request Blocks tab,
18.4.9
In the Auto Config group menu, set the Application to 51, the Tank Num. to the
appropriate value for the attached HART device, and the Sensor to ‘Dual Level’. The HMA
always returns a Dual Level response to Command Uxx? to provide data for the SV output
of the attached HART device.
18.4.10
In the Registers group menu, set the ID to the Poll Address of the attached HART device to
be read for that Tank Num. (Note that due to limitations of the LevelMaster protocol, the
HMA only operates in the Device mode for that protocol.)
18.4.11
Click on ‘Send’.