38
41-621.1 HART
®
to Modbus
®
Adaptor Operating Manual
12.4.2
Change register 3012 to a value of 0. This will cause the HMA to scan the attached
devices at start-up, and record the poll address and other information for each device.
12.4.3
Change DIP switch 1 to ON.
12.4.4
Select Connection\Disconnect from the Modbus Poll menu bar.
12.4.5
Start the Terminal v1.9b application.
12.4.6
Set the COM Port to match the COM port used for the communication cable (the same
number as with the Modbus Poll application).
12.4.7
Set the Baud rate, Data bits, Parity, Stop Bits and Handshaking parameters to match the
settings made in the HMA for LevelMaster communication.
12.4.8
Click Connect.