41-621.1 HART
®
to Modbus
®
Adaptor Operating Manual
61
16.4.16
Select 98
–
Soft Point Parameters for the Point Type, SFP 1
–
Soft Point 01 for the Logical
Number, and 1
–
Float 1 for the Parameter. Note the name for the point, for example, SPF
1, DATA 1.
By checking ‘Show Current Value’, one can confirm that the desired parameter
is being read correctly. Then click ‘OK’ to close the Select TLP dialog.
2
16.4.17
Set a Convert Code (see ROCLINK 800 Help) in the Conversion column () to properly
interpret the data bytes into the correct numerical format.
16.4.18
Assign the correct Comm Port number.
16.4.19
Repeat as required for the remaining parameters to be read from the device.
16.4.20
Return to Master Table tab and ensure that the Comm Status for each line is 8, indicating
a Valid Slave Response.
2
Select ‘Short’ for the Parameter type when setting up to read the unsigned integer communication registers 3000 through
3007 in the HMA.