41-621.1 HART
®
to Modbus
®
Adaptor Operating Manual
25
8.4.16
The supported parameters for the HART devices are listed in Appendices L through S. For
each device, use the appropriate table and the Modbus Register number column labeled
with the Slave ID number of the device. Read the registers for each parameter. Note that
the Slave ID number for the Mbpoll window must match the Slave ID of the HMA, not the
attached HART device(s). For example, to read the PV through QV values for Slave ID 2,
set the Read/Write Definition to:
8.4.17
Ensure that the values displayed match the values shown on the selected
transmitter’s
local user interface.