32
41-621.1 HART
®
to Modbus
®
Adaptor Operating Manual
11.4.
Procedure
11.4.1
Using Procedure 1, ensure that registers 3002 through 3007 of the HMA match the values
shown for the Modbus LevelMaster protocol default settings. Refer to Appendix H for the
HMA Communication settings. If the settings do not match, double-click on a value that
needs to be changed in order to open the Write Single Register dialog, enter the new
value, and then click on Send. Register 3001 can be left at 247.
11.4.2
Change register 3012 to a value of 0. This will cause the HMA to scan the attached
devices at start-up, and record the poll address and other information for each attached
HART device.