41-621.1 HART
®
to Modbus
®
Adaptor Operating Manual
17.5.12
For the Advanced tab,
17.5.13
Ensure that the Data Bits, Parity and Stop Bits match the selections made in step 17.1.1.
17.5.14
Ensure that the Unkey Delay is less than 7 milliseconds as the HMA typically responds
within about 8 milliseconds. If the Unkey Delay time is too long, the XRC will start
listening for a response after the HMA has already started transmitting. As a result, the
XRC will not recognize the response.